throbber
/5;2 :2
`
`{R i c Eqngsmifis
`
`AND ZONED HEATING
`
`MODULATING FURNACE a, I
`SYSTEM DEVELOPMENT aVI
`
`FINAL REPORT
`July 1987 — December 1989
`
`
`
`fil I
`firl
`
`
`
`GasResearchinstitute
`arl
`
`8600 West Bryn Mawr Avenue
`Chicago, Illinois 60631
`
`
`
`HONEYWELL — EXHIBIT 1002
`
`HONEYWELL - EXHIBIT 1002
`
`

`

`Report No. Til-150901691
`
`GRI-91/0075
`
`R E C E I V i"; :3
`
`AUG : ,9 1391
`DEVIYICE OF
`339""“"" A mnAQwYRATW‘":
`
`MODULATING FURNACE AND ZONED HEATING SYSTEM DEVELOPMENT
`
`FINAL REPORT
`July 1987 - December 1989
`
`Prepued by:
`8. J. Feldman. at 1:1.
`
`Tecogen Inc.
`45 First Avenue
`P.O. Box 9046
`Waltham. Massachusetts 02254—9046
`
`Prepared for:
`
`GAS RESEARCH INSTITUTE
`Contract No. Gum-50874454522
`
`Building System- Research
`
`January 1991
`
`

`

`Gm DISCLAIMER
`
`LEGAL NOTICE —~ This report was prepared by Tecogen Inc.. a subsidiary of
`Thermo Electron Corporation. as an account ofwork sponsored by the
`Gas Research Institute [GRIL Neither GR]. members of GRI. nor any person acting
`on behalf of either:
`
`:1. Makes any warranty or representation, express or implied. with respect
`to the accuracy. completeness. or usefulness ofthe information
`contained in this report. or that the use of any information. apparatus.
`method. or process disclosed in this report may not infringe privately
`owned rights: or
`
`b. Assumes any liability with respect to the use of. or for damages resulting
`from the use of. any information. apparatus. method, or process
`disclosed in this report.
`
`

`

`lillllllllllllllllllIiIiiiiiiiiiliiiiiiiliilllllllllllll
`
`I. Dowel D!!!
`January 1991
`
`C.
`
`502724]
`L heron! no.
`REPORT DOCUMENTAHON
`
`
`GRl-91/0075
`PAGE
`
`
`4. 7’“. Ind Whittle
`
`
`
`Modulating Furnace and Zoned Heating System Development
`1. MW“)
`
`l. Foaming Organisation loot. Mo.
`
`S.J. Feldman et al.
`TRQSOB’OlG-S‘l
`9. Performing Organisation Home Ind Address
`
`IO. WIT-“Moth UM "C.
`
`
`
`Tecogen Inc.
`u. tantrum?) or ammo) Ne.
`45 First Avenue
`
`P.0. Box 9046
`(Cl5087’2hs-1522
`
`02254‘9046
`
`
`Waltham, Massachusetts
`
`“D
`
`
`11. Sponsoring Org-Mullen Name Ind Adams
`It. Type 00 Report I. foiled Covered
`
`
`Gas Research Institute
`Final Report
`
`
`
`' 8600 West Bryn Mawr Avenue
`Jul
`1987 - December 1989
`
`60631
`Chicago, lllinois
`
`
`ll. Iupplememuy "do:
`
`
`
`
`«1.. Matteo! (Unit: 200 W6!)
`
`
`
` This report describes an experimental modulating furnace and a zoned warm air heating system for use
`
`in residences.
`The system was installed and tested at the National Association of Home Builders'
`(NAHB) SMART HOUSE in Bowie, Maryland.
`The key features of this system include:
`(1) continuous
`
`
`
`
`modulation of firing rate and supply air over a wide range,
`(2) closed-loop control
`to maintain a
`
`
`desired supply air flow under varying system resistances,
`(3) continuous modulation of combustion
`
`
`air to maintain efficiency,
`(4) a proportional-integral control algorithm operating on measured
`
`
`
`temperatures and set points in each zone to set the furnace firing rate,
`(5)
`low-cost on/off dampers
`to direct air flow to those zones calling for heat, and (6) a single microprocessor—based controller
`
`
`that integrates all aspects of the system.
`
`17. Document Mow.
`
`a. Outflow“
`
`Residential warm-air heating systems
`Residential zone heating
`Residential modulating furnace
`
`I. Milieu/MW“ You!“
`
`:. COM“ Field/EMF
`
`m. nun-mm 3:an
`
`UM WWW
`(5.. mat-nus)
`
`
`no. ”out; cu... mm upon)
`2:. No. 0' n...
`Unclassified
`“6
`a. Security cl.” rm. no) P
`8“ Instructions on nmm
`omen». mm 212 u—m
`(formerly HHS-)5)
`Department of Commute.
`
`

`

`RESEARCH SUM'MARY
`
`TITLE
`
`Modulating Furnace and Zoned Heating System
`Development
`
`CONTRACTOR
`
`Tecogen Inc.
`GRI Contract Number: 5087445-1522
`
`PRINCIPAL
`INVESTIGATORS
`
`S.J. Feldman. D. Bartz. E. Doyle. J. Tandler.
`andA Lowenstein
`
`REPORT PERIOD
`
`July 1987 — December 1989
`Final Report
`
`OBJECTIVES
`
`TECHNICAL
`PERSPECTIVE
`
`RESULTS
`
`Development of a continuously modulating residential gas
`furnace and a zoned heating system.
`
`GRI's support for the development of the modulating furnace
`will accelerate the introduction of this needed product into
`the marketplace. This product will bring to gas consumers
`unprecedented levels of comfort and convenience.
`It‘s the
`next logical step in the evolution of space conditioning.
`When coupled with zoning. the modulating furnace can offer
`significant energy savings.
`
`Some of the benefits provided by a modulating furnace
`include: (I) reductions in electrical consumption,
`(2) reductions in cycling frequency. (3) improvements in
`comfort due to greater temperature uniformity.
`(4) reductions in noise. (5) an improvement in seasonal
`efficiency. and (6) efficient operation of the furnace in an
`arrangement where many small zones need to be serviced.
`
`Fumace manufacturers need a new top-of-the-line product.
`The modulating furnace is the ideal candidate. but before
`they can achieve this goal. outstanding development issues
`must be solved.
`
`Tecogen developed for GRI an experimental modulating
`furnace and a zoned warm air heating system for use in
`residences. The key features of this system include:
`(1) continuous modulation of firing rate and supply air over
`a wide range. (2) closed-loop control to maintain a desired
`supply air flow under varying system resistances,
`(3) continuous modulation of combustion air to maintain
`efficiency. (4) a proportional-integral control algorithm
`operating on measured temperatures and set points in each
`zone to set the furnace firing rate. (5) low-cost on/off
`dampers to direct air flow to those zones calling for heat. and
`(6) a single microprocessor—based controller that integrates
`all aspects of the system.
`
`

`

`
`
`modulation and zoning and the benefits they oifer. Testing
`provided valuable data on different control algorithms and
`brought to the fore the outstanding technical issues
`
`TECHNICAL
`APPROACH
`
`PROJECT
`IMPLICATIONS
`
`The approach taken in developing the modulating furnace
`recognized that commercialization would be difficult if
`significant changes were made to the furnace's basic design.
`So the emphasis was on developing a retrofittable "controls
`package" for converting fixed-firing rate furnaces to
`modulation. The goal was to develop an experimental
`version of this controls package and to show how it works in
`the field.
`
`This project was supported by GRI to develop a new
`residential heating system that has the comfort benefits
`associated with modulation and the energy savings potential
`associated with zoning. The zoned wann-air heating system
`
`This project produced results on the performance of the
`furnace under a variety of operating conditions in the
`laboratory and in a research house with a zoned warm-air
`distribution system. Future research is planned to refine
`the control system and evaluate commercial opportunities.
`
`Larry Brand
`GRI Project Manager
`
`

`

`TABLE OF CONTENTS
`
`RESEARCH SUMMARY .......................................
`
`1. EXECUTIVE SUMMARY ...................................
`
`l. 1 OVERVIEW .........................................
`
`1.2 RA'IIONAIE .........................................
`
`1.3 ACCOMPLISHMENTS ..................................
`
`1.4 RECOMMENDATIONS .................................
`
`2. WORK PERFORMED ......................................
`
`2.1
`
`INTRODUCTION .......................................
`2.1.1 Program Scope .................................
`2. 1.2 Technical Approach .............................
`2.1.3 Elements of the SMART HOUSE System ..............
`
`2.2 SMAR’I‘ HOUSE SYSTEM DESCRIPTION ...................
`2.2.1 Furnace ......................................
`2.2.2 Gas Control ...................................
`2.2.3 Circulating Air Control ...........................
`2.2.4 Combustion Air Control ..........................
`2.2.5 Hard-Wired Control Logic .........................
`2.2.6 Single-Board Controller ..........................
`2.2.7 Data Acquisition and Monitoring ...................
`2.2.8 Zone Control ..................................
`2.2.9
`SMARI‘ HOUSE ................................
`
`2.3 FINDINGS FROM SMART HOUSE TESTS ...................
`2.3.1
`Single-Zone Operation ...........................
`2.3.2 Multi-Zone Operation ............................
`
`2.4 SEASONAL PERFORMANCE ANALYSIS ....................
`2.4.1 Results .......................................
`2.4.2 Definition of the Load ...........................
`2.4.3 Definition of the Conventional Furnace ..............
`2.4.4 Definition of the Modulating Furnace ................
`
`v
`
`1
`
`1
`
`2
`
`3
`
`3
`
`7
`
`7
`7
`7
`10
`
`10
`10
`13
`13
`15
`15
`19
`2 1
`2 1
`23
`
`23
`23
`33
`
`38
`38
`41
`41
`43
`
`

`

`LIST OF ILLUSTRATIONS
`
`2.1
`
`2.2
`
`2.3
`
`2.4
`
`2.5
`
`2.6
`
`2.7
`
`2.8
`
`2.9
`
`2.10
`
`2.11
`
`2.12
`
`2.13
`
`2.14
`
`2.15
`
`2.16
`
`2.17
`
`2.18
`
`2.19
`
`2.20
`
`2.21
`
`Test Facility .........
`
`................................
`
`Typical Operating Envelope for a Furnace Operating
`................................
`at a Fixed Air Flow Rate
`
`Elements of the SMAKI‘ HOUSE System ....................
`
`Furnace Used at the SMART HOUSE ......................
`
`Desired and Actual Gas Control During a Typical Period
`................................
`at the SMART HOUSE .
`.
`
`Desired and Actual Circulating Air Flow Rate
`During a Typical Period at the SMART HOUSE ...............
`
`Circulating Air Fiow Rate Control Schedule ..................
`
`Factory—Wired Control Logic .............................
`
`Control Logic Used with Microprocessor ....................
`
`Single-Zone Control: Typical Day ........ . ................
`
`Single-Zone Control: Low Load ................... . .......
`
`Single-Zone Control: High Load ..........................
`
`Single-Zone Control: Qmt Based on Historical Load ...........
`
`Single-Zone Control: High Gains .........................
`
`Mum-Zone Control: Zone Units Proportioncd to Supply Registers
`
`Multi—Zone Control: Zone Temperatures ....................
`
`Mum—Zone Control: ZU2 = 4-0 Percent .....................
`
`Mum-Zone Control: Basement Unconditioned ...............
`
`Seasonal Heating Load Profile ............................
`
`Standard Thermostat Cycling Rate ........................
`................................
`
`Strategy for Modulation
`
`ll
`
`12
`
`14
`
`16
`
`l7
`
`18
`
`20
`
`27
`
`28
`
`29
`
`30
`
`32
`
`34
`
`35
`
`36
`
`37
`
`42
`
`45
`
`

`

`LIST OF TABLES
`
`2.1
`
`2.2
`
`2.3
`
`2.4
`
`Values of Zone Control Parameters ........................
`
`SMART HOUSE Zone Description .........................
`
`Seasonal Energy Consumption ...........................
`
`Seasonal Operating Costs ...............................
`
`24
`
`25
`
`39
`
`

`

`1. EXECUTIVE SUMIMARY
`
`1.1
`
`OVERVIEW
`
`Tecogen developed for GRI an experimental modulating furnace and a zoned
`warm air heating system for use in residences. The key features of this system
`include:
`i 1) continuous modulation of firing rate and supply air over a wide range.
`
`(2) closed-loop control to maintain a desired supply air flow under varying system
`resistances (3) continuous modulation of combustion air to maintain efficiency.
`(4) a proportional-integral control algorithm operating on measured temperatures
`and set points in each zone to set the furnace firing rate. (5) low-cost on/ off
`dampers to direct air flow to those zones calling for heat. and (6) a single
`microprocessor-based controller that integrates all aspects of the system.
`
`Rather than designing from scratch a furnace or a burner optimized for
`modulation. the approach taken was to develop a factory installable "controls
`package" for converting existing fixed-firing rate furnaces to modulation. Starting
`from scratch would make commercialization difficult because it would force
`
`manufacturers to invest heavily to retool for the new design. The goal was to
`attract a furnace manufacturer by developing an experimental version of the
`controls package and demonstrating it in the field. The field test site was the
`National Association of Home Builders' (NAHB) SMART HOUSE in Bowie. Maryland.
`
`Development of the modulating furnace was limited to its application to
`high-efficiency condensing furnaces.
`It was felt that the modulating furnace would
`initially be marketed as a top«of—the—line product and as such would have to have
`as a base system the most efficient furnace available.
`
`Pulse combustion systems are an important element of the condensing
`furnace market but were outside the scope of this prog‘am.
`it may be possible to
`modulate pulse combustion systems. but this program focused exclusively on
`induced draft systems since these Were the prevalent designs at the time of the
`program.
`
`Zone temperature control at the SMART HOUSE was accomplished using a
`combination of feedback and feedforward control. The feedforward algorithm
`estimates the house load based on either historical energy use (a time average of
`the firing rate over the previous two hours): or outside air temperature, zone
`setpoints. and an assumed UA Both methods were tested. The feedback algorithm
`corrects the estimate by comparing current temperatures with setpoints. The result
`of this computation is a "desired" furnace firing rate that should very closely match
`the load.
`
`

`

`
`
`if it's underflmig or cycles more often if it's overm-ing. but since combustion air is
`also open loop. proper stoichiometry is not guaranteed. fins is an area needing
`further attention.
`
`Combined gas and electric operating cost savings of about 8 percent are
`projected for the modulating furnace operating in a single-zone system. (Based on
`Boston weather data.) With zoning. even larger savIngs are possible.
`
`

`

`1.3
`
`ACCOWLISHMENTS
`
`'l‘ecogen built two modulating furnaces with zone control under 6121
`sponsorship. One was installed at the Natioi'ial Association of Home Builders'
`(MAI-IE) SMART HOUSE in Bowie. Maryland. and the other in Teoogen's laboratory.
`The SMART HOUSE unit operated reliably for 3 months during the 1989 winter.
`These two units were experimental and were designed to evaluate the modulation
`and zoning and the benefits they offer. While they are not commercially viable
`systems in their present form. testing provided valuable data on diiferent control
`algorithms and brought to the fore the many outstanding technical issues.
`
`1 .4
`
`RECOHIMENDATIONS
`
`The experimental system built by Tecogen for GRI demonstrated many of the
`features of a modulating furnace. However. several areas of development are still
`outstanding and must be addressed before a modulating furnace can be
`commercialized.
`
`Without doubt the most important outstanding technical issue is the need
`for a method to control stoichiometry or to keep stoichiornetry within a safe range
`to assure that the CO limit of 400 ppm is not exceeded while modulating. Also. the
`limit must not be exceeded if the flue should be partially or fully blocked. as
`prescribed by ANSI 221.64. The assumption is that one wants to operate as close
`to the CO limit as possible to maintain high thermal efl'iciency.
`
`The present method of using open loop control for both gas and combustion
`air is unacceptable unless appropriate reliable safety switches are incorporated into
`the system. Possible failure paths with the present system include:
`
`(2) Gas valve modulates.
`(1) Gas valve fails to modulate. i.e.. sticks open.
`but to an unpredictable pressure. This may happen because of manufacturing
`tolerances. changes in valve performance over time. or changes in valve
`performance resulting from changes in ambient conditions.
`(3) Gas valve
`modulates to the right pressure. but changes in gas composition or density alters
`gas mass flow. air-fuel ratio and combustion process.
`
`If a reliable low-cost CO "switch" were available. then the present system
`would be acceptable. except a new modulating gas valve needs to be developed.
`The valve should combine the features of the standard combination gas control
`valve and the modulating/regulating valve used at the SMART HOUSE. The key
`technical specification is a 4:1 turndown or greater. High turndown allows
`servicing of small zones. greater numbers of zones. and operation with fewer
`furnace cycles. Existing modulating/regulating valves have only a 2.0 to 2.6:]
`turndown.
`
`

`

`
`
`reliability for this application.
`
`Developing an appropriate method for stoichiometry control must also be
`coordinated with those responsible for developing safety standards. Standard-
`
`The present system uses a proportional-integral (PI) based algorithm with
`a feed-forward estimate of load to set the firing rate. This approach worked well at
`the SMART HOUSE, but further testing is needed. The proposed algorithm was
`tested for one season in one house. A much broader sample tested under a variety
`of situations — different loads. housing types. climates. usage patterns. etc. - is
`needed. Also. several changes need to be incorporated into the algorithm based on
`lessons learned from the SMART HOUSE tests.
`
`

`

`thermostat? Should the thermostats simply be l/O-sensor terminals networked to
`a central processor in the furnace? This would lower the cost per thermostat.
`which is critical for stimulating a market for zoning. Or. should each thermostat
`have processor capabilities on its own? This allows modulating thermostats to, be
`sold separately from modulating furnaces. in the same way that thermostats and
`furnaces are now sold.
`
`is it worth the cost of making the thermostats a two-wire system? Doing so
`would lower installation cost in retrofit situations because all present heating
`systems have at least two wires. Also. should the furnace and thermostat use a
`communication protocol compatible with CEBus or SMART HOUSE? Such systems
`may be the "wave-of-the future."
`
`The thermostat must be capable of operating the air conditioner. How will
`this affect the design of the thermostat? Must one thermostat be capable of
`operating both variable-capacity and smgle-capacity air conditioners? This project
`did not address air conditioning needs.
`
`

`

`

`

`2. WORK PERFORMED
`
`2. 1
`
`INTRODUCTION
`
`2-1-1W
`
`The goal of this project was to develop a continuously modulating residential
`gas furnace and zoning system.
`
`Development of the modulating technolog was limited to its application on
`high-efficiency condensing furnaces. This type of furnace was chosen because it
`is the type most amenable to conversion for modulation.
`
`2. 1.2
`
`e hnical
`
`roach
`
`Furnace design is governed by three independent parameters: firing rate.
`circulating air flow rate. and combustion air flow rate. The first step in the program‘
`was to build a test rig (Figure 2.1) where the efl‘ects of independently varying these
`parameters could be measured.
`in so doing it was possible to define an operating
`envelope for the furnace. The boundaries of this envelope are governed by design
`limits such as the point where condensate forms in the primary heat acchanger. the
`point where excessive heat exchanger temperatures are reached. the point where
`too hot or too cold supply air temperatures are reached, and the point where
`excessive carbon monoxide is generated.
`
`Figure 2.2 shows one such operating envelope. The data were taken at a
`fixed circulating air flow rate. This particular furnace's design point is shown by
`the square in the figure. The effects of moving ofi' the design point are clearly seen.
`For example. the condensation limit is reached at or about 68 MBtu/hr if excess
`air and circulating air flow rates remain constant while firing rate is decreased.
`Avoiding this limit while reducing firing rate even further requires increasing access
`air.
`if this is done efilciency decreases somewhat. Maps like this were used to aid
`in developing control strategies for the modulating furnace.
`
`Zone temperature control at the SMART HOUSE was accomplished using a
`combination of feedback and feedforward control loops. The feedforward algorithm
`calculates the nominal house load based on either historical energy use or outside
`air temperature and zone setpoints. Both methods were tried. The feedback
`algorithm calculates a correction to this nominal load based on a comparison of
`current temperatures and setpolnts.
`
`

`

`
`
`DISCHARGE
`
`COOLING
`
`167-188r
`
`CEILING
`
`BLOWER
`
`TEST FURNACE
`
`BOOSTER
`
`FLOOR
`
`Figure 2.1 Test Facility
`
`

`

`meumhu...
`
`Egg/mum,,r,
`
`onecomcomon“
`
`ANVmH<mmmuxw
`
`>m<szm2Honp<mztzou
`
`./
`
`memmEéEzEmém/%\\\K1/;1/I;a;/\f\\\
`
`III(”4‘O‘V\’D
`
`
`
`Szszw/mow,4%,
`
`III
`
`am
`
`0v
`
`om
`
`om
`
`(spuosnoql)
`
`(H/nuaw> 31V8 SNIHIJ
`
`
`
`3mm30EL_<68:".manmczmhmao085:“.ahemao_m>cwmczeao.333.~.~83mm“.
`
`
`
`
`
`
`
`
`

`

`
`
`analysis. The microprocessor controlled the inducer motor. circulating air motor
`
`modulating furnace would couple to a zoned system. and (3) sewe as platform for
`testing hardware and various furnace and zone control algorithms.
`
`2.2
`
`SMART HOUSE SYSTEM DESCRIPTION
`
`2.2. 1 Furnace
`
`The furnace tested at the SMART HOUSE was a modified version ofa
`commercial condensing furnace with a rated input of 100 MBtu/hr and an AFUE
`of 90.5 percent.
`it was designed to operate with a temperature rise between 50°
`and 80°F. This implies an air flow rate between 1
`
`anger cells the test furnace actually had
`foul-J The furnace uses aluminized steel multi-port burners which fire up into
`glass~1med primary heat exchanger cells. Combustion gm pass through the cells
`
`secondary heat exchanger assembly. This assembly consists of three staggered
`rows of half-inch diameter stainless-steel tu
`enhance heat transfer. Aluminum fins are attached to these tubes to enhance heat
`transfer to the circulating air.
`
`10
`
`

`

`5N3“:
`
`mmEmeD
`
`hzmimm<m
`
`l'lll'l'lll'l'lII-IIII
`D
`
`
`
`
`
`239$mmno:5.5%.2:ho3:95522:9”.
`
`‘quo 30'"!
`
`na-
`
`$40
`
`ll
`
`wZON
`
`mmmDh<mwn3mh
`
`
`

`

`
`
`PRIMARY
`HEAT
`EXCHANGER
`
`71-168
`
`"is INTERCONNECTING
`PIPE
`
`SECONDARY
`HEAT
`EXCHANGER
`
`" CIRCULATING
`AIR BLOWER
`
`
`
`
`
`INDUCER'
`BLOWER
`
`=
`2':
`
`"
`
`BURNERS
`
`GAS
`VALVE .
`
`s
`CONTROL "
`MODULE ;
`
`Figure 2.4 Furnace Used at
`
`the SMART HOUSE
`
`12
`
`

`

`The multi-port burners were easily modulated. By adjusting excess air
`levels. a stable blue flame was maintained at inputs less than 20 MBtuh/hr. over
`a five-to-one turndown.
`
`This furnace is not a direct vent type; combustion air is drawn from the
`space around the furnace. not ducted from outside. So the unmodified unit was
`certified per ANSI 22 1.47. American National S tandarclfor Gas-Fired Central
`Fumaoes {Except Direct Vent and Separated Combustion System Central Muses).
`Most furnaces in the future will be the direct-vent type and will be certified under
`ANSI standard 221 .64.
`
`2.2.2 Gee Control
`
`An experimental modulating]regulating valve made by Maidtrol Corporation
`(Model E5281) controlled firing rate.
`it was placed in series with and downstream
`from the Honeywell CGC (combination gas control) valve that comes standard with
`the furnace. This configuration made it necessary to slightly increase the 060's
`normal setpoint of 3.5 MG [inches water column. gauge) to 3.8 M0 to overcome
`the added pressure drop of the Maxitrol valve. The Maxitrol valve regulated
`manifold pressure between 3.5 and 0.32 IWG. Pressure regulation was controlled
`by voltage to the valve. Higher voltages resulted in higher pressures. Power to the
`valve was applied in a pulse-width-modulated fashion because this reduced
`hysteresis.
`
`Data in Figure 2.5. which covers a ten-hour period on a typical day at the
`SMART HOUSE. shows valve performance to be excellent. The dotted line shows
`
`the desired firing rate. The actual firing rate. as measured by a mass flow meter.
`is shown by the solid line. From this we see the valve is fast-responding and
`accurate over the full modulating range of 100 to 30 MBtu/ hr.
`
`2.2.3 Circulating Air Control
`
`'l‘ecogen replaced the standard circulating air blower motor in the furnace
`with a General Electric brushless DC motor. An electronics module, also provided
`
`by GE. controlled the motor's speed using electrical commutation. The
`motor/ controller package. called an ECM (electrically commutated motor). has a
`better cost/benefit ratio when compared with alternative methods of speed control
`for this application such as inverter-drives or SCR‘s.
`
`Tecogen developed a method to achieve wide-ranging closed-le control of
`air flow under varying system resistances using the controller’s tachometer output.
`This approach made it unnecessary to use costly temperature or pressure
`transducers to achieve the same end.
`
`13
`
`

`

`EN-3E.
`
`5:
`
`«a2.ooe
`
`@565us:
`
`
`
`Gum—mun........
`
`
`
`-_<=._.0<1'
`
`(an/mew) suvu smau
`
`14
`
`
`
`
`
`
`
`
`
`wmno:FMS;9:«mDatum:83»...m9.1.5.9550m5_m30<ucmUmtmoam.~9.sz
`
`
`
`

`

`Closed-loop control of air flow at the SMARI‘ HOUSE is shown in Figure 2.6.
`The graph shows a typical 19-hour period during which the desired flow rate.
`shown as the dotted line. varied from 1300 cfm to 845 cfm. The actual flow rate.
`as measured by a velocity probe. is shown as a solid line and follows closely the
`desired value.
`
`For a single-zone operation. the desired flow rate is scheduled with furnace
`input following the function shown in Figure 2.7. Flow rate decreases in proportion
`to input during the first half of tum-down. keeping temperature rise fixed. Then,
`during the last half. flow rate is constant allowing temperature rise to decrease.
`The break at the half-way point was chosen arbitrarily. A careful cost-benefit
`analysis would have to be performed to determine the best break point. To
`maximize energy savings. flow rate should decrease throughout the turn-down
`range rather than stopping half way. but adequate velocity pressure is needed to
`overcome duct resistance and to provide good distribution in the heated space.
`
`For multi-aone operation. the desired flow rate should consider the number
`of zones calling and their loads. Had this been done the control schedule would
`have been extended as shown by the dotted line in Figure 2.7. This would have
`allowed the system to operate at lower flow rates.
`
`2.2.4 Qombustlon Air Control
`
`A General Electric ECM was used to drive the inducer blower which was a
`Fasco "Swirlwind" unit.
`
`To maximize combustion efficiency. motor speed was reduced with firing
`rate. This was accomplished by reducing torque. A schedule of torque vs firing rate
`that was set up in the lab and then adjusted in the field always provided enough
`combustion air. As with the circulating air ECM. the inducer ECM also provided
`a tachometer output. but this output could not be used for closed—loop control
`because the fan characteristics of the Swirlwmd blower were not the same as those
`of the circulating air blower. A matched blower/motor set is needed for closed—loop
`control. The tachometer output. however. was used as a safety device as follows:
`At any given torque. a certain speed is expected.
`if at least that speed is not
`achieved. it can be assumed that the motor has failed and the gas should be shut
`off, This safety feature was used at the SMART HOUSE.
`
`2.2.5 Hard-Wired Control Logic
`
`The test furnace comes from the factory hardwired with control logic that
`properly interfaces the furnace with the thermostat and with safety devices.
`Figure 2.8 shows this in ladder-logic form. The thermostat. with its four terminals
`R. G. Y. and W. is inside the dotted box.
`
`15
`
`

`

`Fang
`
`.35.!mmno5anRmu
`
`mm
`
`6505ms:
`
`v;
`
`né
`
`«4.
`
`».w
`
`ad
`
`ad
`
`he
`
`9:
`
`ad
`
`«.0
`
`n6
`
`NA.
`
`.3
`
`
`
`$20:5:252:3vote“..835m9.35£3.22".:<95285.52up;3:30
`
`
`
`
`
`
`
`
`
`(spuesnou1)
`
`(was) Elva MO‘H NVJ
`
`16
`
`
`
`min0.5mm
`
`
`
`
`

`

`car
`
`MZON._._.4:S
`
`20F<mmmo
`
`MZONmSGz—m
`
`202.55%.
`
`
`38on8on88
`£323:".0.Fzmommause.532.
`
`SHE EauucumEtcou2mm30EL_<mama—autoWm959”.
`
`cor
`
`cm
`
`3
`
`2.
`
`on
`
`om
`
`3
`
`on
`
`(wnmwi :IO lNBOHad)31VH MO'H
`
`17
`
`

`

`TF84-291
`
`VOLTAGE
`
`(BURNER)
`
`HONEYWELL
`SGSGD
`
`CAUTION-
`HIGH
`
`Figure 2.8 Factory»Wired Control Logic
`
`18
`
`

`

`The sequence of operations in a normal heating cycle is as follows: Voltage
`is applied to terminal W when the thermostat calls for heat.
`lDR is energized
`through NPC and contacts 3~I and 6-4 close. When contacts 3-1 close. IBM is
`energized. When IDM has achieved a suilicient speed. NPC closes (contacts 6-4
`keep lDR energized while NPC closes). When NPC closes, the Honeywell ignition
`controller is energized provided LC. OTS. and EDS are closed. The ignition
`controller has a time delay for purging the combustion passages. After the purge
`period. the pilot is lit followed by the main burner. As the plenum heats, BFC
`closes. which energizes iBM.
`If HCR is energized. which happens when the fan
`on/ auto switch is in the on position and terminal G is powered. IBM will have been
`continuously energized and typically operating on high speed. The gas will stay on
`until either the thermostat is satisfied or one of the safety devices opens. As the
`
`plenum cools. BFC opens. which de-energizes IBM. This completes the cycle.
`
`The modulating furnace uses the same sequence of operations described
`above during startup and shutdown However. when modulating. NPC is locked out
`because inducer speed is reduced below its setpoint and would otherwise shut the
`gas off. Thus. NPC is only proved at startup.
`
`Tecogen‘s use of a microprocessor made it necessary to rewire the furnace.
`The new ladder-logic diagram is shown in Figure 2.9. As shown. the status of
`several switches is monitored by the microprocessor. For example. LC. OTS. and
`EDS are monitored via optically-coupled relays. Should these switches open. the
`microprocessor is programmed to halt operation and send an alarm signal to the
`operator.
`
`2.2.6 Single-Board Controller
`
`A microprocessor-based single-board controller was used at the SMART
`HOUSE for control and data acquisition. The control board is a standard Tecogen
`
`product that is used on its cogeneration and engine-driven chiller systems. The
`advantage of using a microprocessor-based system is the flexibility it offers for
`testing various control strategies.
`
`Tecogen's single-board controller combines the Motorola 68000 and
`Microware's UNIX-like. 059 operating system with quality hardware interfaces.
`089 is both a ROMable real time system and a full function disk-based system with
`
`a range of languages. The port includes complete high level software/hardware
`interfaces.
`‘
`
`This board in no way represents what is needed for a commercial unit but
`it offered the needed power during this development phase of the program.
`
`19
`
`

`

`
`
`
`
`10.25am29.50rm?—mum
`
`3”»th
`
`
`
`190853.3in
`
`
`
`>149»zen—.5300!c!
`
`52.5.5mm
`
`
`
`
`
`$9.5633.55cm>owho
`
`
`
`
`
`.552895¢mem>F<auzon:
`
`105SnExec-Eman
`
`
`
`mi;m<o:2:>6:
`
`
`
`u>4<>r40.54!>2
`
`40528.550.. ><._wc
` .55282E530393
`
`
`
`

`

`2.2.7 Data Acguiaition and Monitoring
`
`Data from the single-board controller were sent to an on-site PC. This
`allowed storage of the data for later analysis and provided for real-time viewing of
`the system‘s operation Several data collection and processing computer programs
`were written for the PC to complete data acquisition
`
`2.2.8 Zgne Control
`
`The zone control program determines furnace firing rate and controls the
`on/ofi‘ dampers for the supply and return air ducts for each zone. It tries to
`maintain zone temperatures at their respective setpoints under all conditions when
`a heating load exists. The algorithm has no provisions to handle a cooling load.
`Control "starts" when any zone's temperature drops below its setpoint. Control
`continues so long as the temperature doesn't exceed the setpoint by more than
`two degrees. Above two degrees. control "stops." The basic controlling equation
`used at the SMART HOUSE was:
`
`of... - 3 (we <5.) [19. E. + firm, at + 0...]
`
`.
`
`5
`
`l
`
`where:
`
`where :
`
`qum = desired furnace firing rate (percent of capacity):
`ZUJ
`= zone units of zone 1 (the estimated proportion of the total load due
`to zone 1);
`‘
`= 0 if Tame >
`“We“ + 2). (damper closed). or 1 if Tmne < Twink“.
`(damper open):
`
`81
`
`Ej
`Kp
`K1
`t
`cht
`
`= zone error (Tutpomt — Tum):
`= proportional gain constant:
`r:
`integral gain constant;
`= accumulated time after 81 becomes unity;
`= estimated heat load. or feed forward signal.
`
`The proportional gain is determined as:
`
`K9 3 QM mJEm-z
`
`= maximum furnace capacity (100%);
`qum max ll
`maximum error allowed (10°F).
`
`21
`
`

`

`
`
`The integral gain for a critically damped system is:
`
`K‘ =Kp/1:
`
`where:
`
`r = system time constant (500 seconds. as determined from experiment).
`
`The estimated heat load (9:39 is determined by two difl‘erent methods: UA
`and historical load. Tests were conducted on both methods.
`
`The equation for the UA method is:
`
`0. = UA 5w - rrm + sum» capacity)
`
`estimated overall heat transfer coeflicient it outside surface
`area:
`
`average value of zone setpoints:
`= outdoor air temperature adjusted to account for thermal
`capacitance of house;
`
`It
`
`maximum output of furnace (90 MBtu/ hr).
`
`where:
`
`(qum)i
`At
`
`[I
`H
`
`furnace firing rate at time Increment 1;
`sampling period;
`
`time period over which Qest is determined.
`
`22
`
`

`

`The value ZUj was selected for each zone to reflect the heat load of that zone
`relative to the total. When zone j calls for heat with other zones OK. it receives the
`heat output to match its load.
`
`It was assumed that zone

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket