CHICO® SpeedSeal™ Compound
`Fast Acting Sealing Compound
`Sealing Fitting Modification Kit
`For Use with Crouse-Hinds EYS Sealing Fittings
`Installation & Maintenance Information
`SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
`
`IF 1457
`
`CAUTION
`CHICO SpeedSeal compound is to be used only with Cooper Crouse-Hinds
`EYS type sealing fittings in ½" to 2" trade sizes. SpeedSeal compound is
`suitable for Class I, Division 1 and 2, Groups C & D and Class II,
`Division 1 and 2, Groups E, F & G hazardous areas only, even when
`used in a fitting rated for Group B.
`
`CAUTION
`The temperature of the SpeedSeal compound must be between 50°F (10°C)
`and 85°F (29°C) before mixing. Sealing fittings must be at a temperature
`above 40° F (4°C).
`
`CAUTION
`Wear proper eye protection and protective plastic gloves when mixing and
`injecting SpeedSeal compound.
`
`WARNING
`Contents will develop internal pressure after mixing, remove mixing rod
`immediately after mixing to prevent pressure buildup and possible sudden
`eruption that could result in personal injury
`
`Contains isocyanate - may be skin and respiratory sensitizer. May cause
`irritation of eyes, skin, nose and throat.
`
`The SpeedSeal compound will expand to 4 times its original volume when
`cured.
`
`Do not breathe vapors. Use with adequate ventilation. Avoid contact with
`eyes, skin and clothing.
`
`APPLICATION
`
`The National Electrical Code® (NEC) in Article 501, Section 501-5, requires that
`seals be installed in specific places in Class I, Divisions 1 and 2 classified areas.
`This is to minimize the passage of gases and vapors and prevents the passage of
`flames through the conduit from one portion of the electrical installation to another
`portion.
`
`While not a code requirement, it is considered good practice to sectionalize long
`conduit runs by inserting seals not more than 50 to 100 feet apart, depending on the
`conduit size, to minimize the effects of "pressure piling".
`
`The NEC in Section 502-5 requires seals in Class II locations under certain
`conditions. Cooper Crouse-Hinds sealing fittings can be used to meet these
`requirements.
`
`Conduit seals are not intended to prevent the passage of liquids, gases or vapors at
`a continuous pressure differential across the seal. Even at differences in pressure
`across the seal equivalent to a few inches of water, there may be a slow passage of
`gas or vapor through a seal and through the conductors passing through the seal.
`
`Cooper Crouse-Hinds sealing fittings are listed by Underwriter's Laboratories, Inc.
`(UL), for use in Class I and Class II hazardous locations with Chico A sealing
`compound and Chico X fiber. Alternatively, Cooper Crouse-Hinds EYS type sealing
`fittings are also UL listed for use in Class I, Division 1 and 2, Groups C & D and
`Class II, Division 1 and 2, Groups E, F & G hazardous areas with Cooper Crouse-
`Hinds SpeedSeal sealing compound.
`
`Cooper Crouse-Hinds CHICO SpeedSeal compound may be used to seal in both
`horizontal and vertical installations. It may be used with type EYS sealing fittings in
`½" to 2" trade sizes, in Class I, Division 1 and 2, Group C and D and Class II,
`Division 1 and 2, Groups E, F & G hazardous areas. The SpeedSeal compound
`must be used with Chico X fiber in vertical installations. The Chico X fiber is used to
`create a dam to prevent the SpeedSeal material from running down the conduit
`system before it sets. Damming is not required in horizontal conduit runs. However,
`if you want to prevent the sealing compound from expanding into conduit, Chico X
`fiber dams should be used in the sealing fittings integral bushings.
`
`SpeedSeal compound, when properly mixed, starts to gel in about 4 minutes at 70°F
`(21°C) or 10 minutes at 40°F (4°C) into a dense, strong mass which is unaffected by
`water, is not attacked by petroleum products and is not softened by heat. It will
`harden within 20 minutes and will withstand, with an ample safety factor, pressure
`from an exploding gas or vapor.
`
`Conductors sealed in SpeedSeal compound should be an approved thermoplastic or
`rubber insulated type.
`
`Installers should be trained before making the dam, mixing and pouring the
`compound. Call Cooper Crouse-Hinds for a copy of the installation video.
`
`INSTALLATION
`
`Figure 1 - SpeedSeal Compound Chart
`Use chart to determine which size
`SpeedSeal cartridge to use for selected
`sealing fitting.
`
`CHICO SS2 (2 oz.)
`CHICO SS6 (6 oz.)
`
`Fitting
`Catalog Number
`
`Amount of
`SpeedSeal material
`needed (in ounces)
`
`Suggested
`SpeedSeal
`Catalog Number
`
`EYS1, EYS16, EYS11, EYS116
`EYD1, EYD16, EYD11, EYD116
`EYS2, EYS26, EYS21, EYS216
`EYD2, EYD26, EYD21, EYD216
`EYSX11, EYDX11
`
`EYS3, EYS36, EYS31, EYS316
`EYD3, EYD36, EYD31, EYD316
`EYSX21, EYDX21
`
`EYS41, EYS416, EYS4, EYS46
`EYD4, EYD46, EYD41, EYD416
`EYS51, EYS516, EYS5, EYS56
`EYD5, EYD56, EYD51, EYD516
`EYSX31, EYDX31
`EYSX41, EYDX41
`
`EYS61, EYS616, EYS6, EYS66
`EYD6, EYD66, EYD61, EYD616
`EYSX51, EYDX51
`
`1
`
`2
`
`3
`
`6
`
`CHICO SS2
`(2 oz. Cartridge)
`
`CHICO SS2
`(2 oz. Cartridge)
`
`CHICO SS6
`(6 oz. Cartridge)
`
`CHICO SS6
`(6 oz. Cartridge)
`
`IF 1457 (cid:127) 03/03
`
`Copyright © 2003, Cooper Industries, Inc.
`
`Page 1
`
`Cooper Ex. 1009
`
`

`

`Preparing Sealing Fittings
`
`1.
`
`Remove the pipe plug(s) from the EYS sealing fitting. See Figure 1.
`
`Figure 1
`
`2.
`
`3.
`
`4.
`
`5.
`
`6.
`
`7.
`
`For vertical installations use Chico X fiber to make a dam in the bottom
`conduit hub. The dam will prevent the un-gelled SpeedSeal compound from
`leaking out of the sealing chamber. No dam is required for horizontal
`installations unless it is desired to have compound expand in one direction or
`to keep compound out of conduit.
`
`NOTE: SEPARATION OF INDIVIDUAL CONDUCTORS IS NOT
`REQUIRED - THE SPEEDSEAL COMPOUND WILL SEPARATE THE
`CONDUCTORS AS IT EXPANDS.
`
`To properly make dam in conduit hub, use EYS TOOL KIT or hardwood stick,
`to force the conductors forward. Do not use metal tools.
`
`Pack the fiber into the bottom conduit hub behind the conductors.
`
`Push the conductors towards the back of the fitting and pack fiber in bottom
`conduit hub in front of conductors. It is not critical that the conductors are
`separated because the SpeedSeal compound will expand and fill around the
`individual conductors. However, a good dam is required to prevent the fluid
`material from leaking out of the sealing chamber.
`
`Do not leave any shreds of fiber clinging to the side wall of sealing chamber
`or to the conductors. Such shreds when imbedded in the sealing compound
`may form leakage channels. The completed dam should be even with the
`integral bushing (conduit stop).
`
`In vertical installations, if the EYS sealing fitting is the type with two threaded
`openings replace the threaded plug in the bottom opening. The sealing
`compound will be poured into the top opening. In horizontal installations,
`replace the plug in the smaller opening, the sealing compound will be poured
`into the larger opening. See Figure 2.
`
`Figure 2
`
`Mixing and Dispensing SpeedSeal Compound
`READ ALL INSTRUCTIONS PRIOR TO MIXING. SPEEDSEAL
`1.
`COMPOUND BEGINS TO EXPAND VERY QUICKLY. BE SURE TO
`FAMILIARIZE YOURSELF WITH THE INSTRUCTIONS ON THE
`FOLLOWING PAGES BEFORE MIXING. THIS WILL ENSURE PROPER
`INSTALLATION.
`
`2.
`
`Make sure that SpeedSeal material is at a temperature between 50°F (10°C)
`and 85° F (29°C).
`
`3. WEAR SAFETY GLASSES AND PROTECTIVE GLOVES.
`
`5.
`
`6.
`
`7.
`
`8.
`
`9.
`
`Remove the tape band from the cartridge.
`
`Pull the mixing rod up to the top of the
`cartridge. See Figure 4.
`
`Figure 4
`
`Squeeze the cartridge in the area of the
`removed tape band to deform the foil
`barrier between the two materials.
`See Figure 5.
`
`SQUEEZE
`
`Figure 5
`
`Push the mixing rod all the way in to the bottom of the cartridge (red side).
`
`Mix rapidly for 40 to 50 strokes (a stroke is one complete in and out cycle.)
`While mixing hold cartridge firmly and turn in a clockwise rotation to make
`sure that the plunger is swiping all material in the cartridge. DO NOT MIX
`FOR MORE THAN 30 SECONDS. PRESSURE WILL BUILD UP ON THE
`INSIDE AFTER 30 SECONDS AS THE MATERIAL STARTS TO EXPAND.
`
`10. At the last stroke, push the mixing
`rod all the way in to the bottom (red
`side), grasp the cartridge firmly at
`the bottom to hold plunger in place
`and immediately unscrew the
`mixing rod and remove carefully.
`See Figure 6.
`
`11. Screw nozzle onto cartridge where
`mixing rod was removed. See
`Figure 7.
`
`PUSH
`DOWN &
`UNSCREW
`
`SQUEEZE
`PLUNGER TO
`KEEP IN PLACE
`
`Figure 6
`
`SCREW
`NOZZLE INTO
`CARTRIDGE
`HERE
`
`Figure 7
`
`12. Use the mixing rod to push the plunger. Inject the proper amount of sealing
`compound material into the fitting through the EYS threaded opening. See
`Table 1 at the beginning of installation instructions for proper amount of
`material. Cartridge is marked with incremental 1 ounce segments. See
`Figure 8.
`
`SQUEEZE
`
`4.
`
`Check the mixing rod to
`ensure that it isn't overly
`tight or loose. To do this,
`hold the cartridge with
`the red end cap facing
`up and squeeze the
`cartridge in the area
`around the plunger. This
`will hold plunger in place.
`See Figure 3. Turn
`counterclockwise slightly
`to loosen, then clockwise
`to re-tighten snugly.
`
`Figure 3
`
`Figure 8
`
`IF 1457 (cid:127) 03/03
`
`Copyright © 2003, Cooper Industries, Inc.
`
`Page 2
`
`Cooper Ex. 1009
`
`

`

`13. Replace and tighten the sealing fitting's plug promptly to avoid the
`SpeedSeal compound from gelling and fouling the threads. See Figure 9.
`
`Figure 9
`
`14. SpeedSeal material should be used immediately. After one minute dispose
`of any unused material.
`
`15. After replacing the plugs attach the red nameplate to the sealing fitting with
`the plastic band. Each modification kit is provided with an appropriate
`number of nameplates and bands. Position the nameplate for maximum
`visibility.
`
`Table 35.1 The maximum number of conductors that can be sealed in a fitting
`
`Example of how to use Table 35.1
`
`The maximum number of #4 type THHN conductors (Column B) permitted
`by UL Std. 886 in a 1-1/2” size sealing fitting is 6. The (6) #4 THHN
`conductors represents the maximum wire fill of 25% of less for sealing
`fittings. Increasing the sealing fitting to a 2” trade size will provide space for
`the 40% wire fill, or nine (9) #4 conductors, and comply with UL Std. 886.
`
`Trade
`Size
`1-1/2"
`
`Conductor
`Size
`#4
`
`Type
`THHN (Col.B)
`
`Max No.
`Permitted for
`25% Fill
`6
`
`Max. No. Permitted
`for 40% Fill/Trade
`Size Sealing Fitting
`Needed
`(9/2")
`
`In our example, use an EYS6 (for 2” size EYD, EZD, or EZS) sealing fitting.
`
`The maximum number of wires that can be sealed in a fitting are as follows:
`
`Size
`AWG
`or KCmII
`
`1/2"
`Seal
`(Qty/NPT Size)
`A
`B
`7
`11
`18
`6
`9
`16
`3
`8(13-3/4")
`14
`3
`6(10-3/4")
`12
`10 1(2-3/4")
`4(6-3/4")
`8
`1
`2(3-3/4")
`6
`1
`1
`4
`1
`1
`3
`2
`1
`1/0
`2/0
`3/0
`4/0
`250
`300
`350
`400
`500
`600
`700
`750
`800
`900
`1000
`
`1-1/4"
`1"
`3/4"
`Seal
`Seal
`Seal
`(Qty/NPT Size)
`(Qty/NPT Size)
`(Qty/NPT Size)
`A
`B
`A
`B
`A
`B
`35
`58
`20
`33
`12
`20
`30
`47
`17
`27
`10
`16
`18
`43(69/2")
`10
`24(39/1-1/4")
`6
`15(24/1")
`15
`32(51/2")
`11(18/1") 8(9/1-1/4" 18(29/1-1/4")
`5
`13
`20(32/2")
`4
`7(11/1")
`7
`11(18/1-1/4")
`7
`11(16/1-1/2")
`2
`4(5/1")
`4
`6(9/1-1/4")
`4(6/1-1/4") 4(5/1-1/2"
`7(11/2")
`1
`2(4/1")
`2
`1
`1(2/1")
`1
`2(4/1-1/4")
`3
`4(7/2")
`1
`1
`1
`2(3/1-1/4")
`3
`3(6/2")
`1
`1
`1
`1(3/1-1/4")
`3
`3(5/2")
`1
`1
`1
`1
`1
`2(3/1-1/2")
`1
`1
`1
`1
`2(3/2")
`1
`1
`1
`1(2/1-1/2")
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`
`1-1/2"
`Seal
`(Qty/NPT Size)
`A
`B
`49
`80
`41
`64
`25
`58(94/2")
`21
`43(70/2")
`17(18/2")
`27(44/2")
`9
`16(22/2")
`6
`9(15/2")
`5
`6(9/2")
`4
`5(8/2")
`3(4/2")
`4(7/2")
`3
`3(5/2")
`2
`2(4/2")
`1
`2(3/2")
`1
`1(3/2")
`1
`1(2/2")
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`
`2"
`Seal
`(Qty/NPT Size)
`A
`B
`80
`131
`68
`106
`41
`96(154/3")
`34(35/2-1/2")
`71(114/3")
`29
`45(73/3")
`16
`26(36/2-1/2")
`10(11/2-1/2")
`16(26/3")
`8
`9(16/3")
`7
`8(13/3")
`6
`7(11/3")
`4(5/2-1/2")
`5(8/3")
`4
`4(7/3")
`3
`3(6/3")
`3
`3(5/3")
`2
`2(4/3")
`1
`2(3/2-1/2")
`1
`1(3/1-1/2")
`1
`1(2/1-1/2")
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`
`Col. A = Types RFH-2,
`RH, RHH, RHW, THW,
`TW, XHHW (AWG 14-6),
`FEPB (AWG 6-2).
`
`Col. B - Types FEP,
`THHN, THWN, TFN, PF,
`PGF, XHHW, (AWG
`4-2000 MCM), FEPB
`(AWG 14-8).
`
`All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy
`or completeness thereof are not guaranteed. In accordance with Crouse-Hinds "Terms and Conditions of Sale", and since conditions of use are outside
`our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection
`therewith.
`
`Cooper Industries Inc.
`Crouse-Hinds Division
`PO Box 4999, Syracuse, New York 13221 (cid:127) U.S.A.
`Copyright© 2003, Cooper Industries, Inc.
`
`IF 1457
`Revision 1
`New 03/03
`
`Cooper Ex. 1009
`
`

`

`Le produit SpeedSeal™ CHICO®
`Produit d'étanchéité à action rapide
`Nécessaire de modification des raccords d'étanchéité
`Pour utilisation avec les raccords d'étanchéité
`EYS de Crouse-Hinds
`Instructions d'installation et d'entretienn
`CONSERVEZ CES INSTRUCTIONS POUR CONSULTATION FUTURE
`
`IF 1457
`
`PRÉCAUTION
`Le produit SpeedSeal de CHICO doit être utilisé seulement avec les raccords
`d'étanchéité EYS de Cooper Crouse-Hinds dans les grandeurs commerciales
`de ½" à 2". Le composé SpeedSeal convient à la Classe I, division 1 et 2,
`groupes C et D, et à la Classe II, division 1 et 2, groupes E, F et G dans les
`zones dangereuses seulement, même quand il est utilisé dans un raccord
`classé dans le groupe B.
`
`PRÉCAUTION
`La température du produit SpeedSeal doit se situer entre 10 °C (50 °F) et 30 °C
`(85 °F) avant le mélange. Les raccords d'étanchéité doivent être à une
`température supérieure à 4 °C (40 °F). Le produit SpeedSeal gonflera
`jusqu'à 4 fois son volume original quand il durcit.
`
`APPLICATION
`L'article 501, section 501-5, du National Electrical Code® (NEC) requiert que les
`joints d'étanchéité soient installés dans des endroits spécifiques classés Classe I,
`divisions 1 et 2. Ceci a pour but de minimiser le passage des gaz et des vapeurs et
`d'empêcher le passage de flammes dans les conduits d'une partie à une autre d'une
`installation électrique.
`
`Bien que ce ne soit pas requis par le code, il est considéré comme une bonne
`pratique de segmenter un long conduit en insérant des joints d'étanchéité à des
`distances n'excédant pas 15 à 30 mètres (50 à 100 pieds), selon la dimension du
`conduit, pour minimiser les effets d'une « accumulation de pression ».
`
`La section 502-5 du NEC requiert des joints d'étanchéité dans les endroits de
`Classe II qui présentent certaines conditions. Les raccords d'étanchéité de Cooper
`Crouse-Hinds peuvent être utilisés pour satisfaire ces exigences.
`
`Les joints d'étanchéité des conduits n'ont pas pour but d'empêcher l'écoulement de
`liquides, de gaz ou de vapeurs sous un différentiel de pression continu dans tout le
`joint. Même à des différences de pression dans le joint équivalentes à quelques
`centimètres d'eau, il peut y avoir un lent écoulement de gaz ou de vapeur au travers
`le joint et à travers les conducteurs qui passent par le joint.
`
`Les raccords d'étanchéité de Cooper Crouse-Hinds sont enregistrés par
`Underwriter's Laboratories, Inc. (UL) pour utilisation dans les endroits dangereux de
`Classe I et de Classe II avec le produit d'étanchéité Chico A et la fibre Chico X.
`Selon une autre option, les raccords d'étanchéité de type EYS de Cooper Crouse-
`Hinds sont également enregistrés UL pour utilisation dans les endroits dangereux de
`Classe I, division 1 et 2, groupes C et D, et de Classe II, division 1 et 2, groupes E,
`F et G avec le produit d'étanchéité SpeedSeal de Cooper Crouse-Hinds.
`Le produit SpeedSeal de Cooper Crouse-Hinds peut être utilisé pour le scellement
`d'installations horizontales et verticales. Il peut être utilisé conjointement avec des
`raccords d'étanchéité EYS possédant des dimensions commerciales de ½"à 2" dans
`les endroits dangereux de Classe I, division 1 et 2, groupes C et D, et de Classe II,
`division 1 et 2, groupes E, F et G. Le produit SpeedSeal doit être utilisé avec la fibre
`Chico X dans les installations verticales. La fibre Chico X est utilisée pour créer une
`barrière pour empêcher le produit SpeedSeal de descendre dans le système de
`conduits avant qu'il ne fige.
`
`La barrière n'est pas requise dans les sections horizontales de conduits. Cependant,
`si vous voulez empêcher le produit d'étanchéité de gonfler dans les conduits, les
`barrières de fibres Chico X devraient être utilisées dans les manchons intégrés des
`raccords d'étanchéité.
`
`Le produit SpeedSeal, quand il est correctement mélangé, commence à figer après
`environ 4 minutes à 21 °C (70 °F) ou 10 minutes à 4 °C (40 °F) en une masse
`dense et solide qui n'est pas affectée par l'eau, n'est pas attaquée par les produits
`pétroliers et n'est pas ramollie par la chaleur. Il durcira en moins de 20 minutes et
`résistera, avec une grande marge de sécurité, à la pression d'un gaz ou de vapeurs
`qui explosent.
`
`PRÉCAUTION
`
`Portez une protection oculaire adéquate et des gants de protection de
`plastique quand vous mélangez et injectez le produit SpeedSeal.
`
`AVERTISSEMENT
`Le contenu générera une pression interne après mélange. Enlevez la tige
`d'agitation immédiatement après l'opération de mélange pour empêcher une
`accumulation de pression et une éruption soudaine possible du produit qui
`pourrait résulter en une blessure corporelle.
`
`Contient de l'isocyanate - peut être un sensibilisateur cutané et respiratoire.
`Peut causer une irritation des yeux, de la peau, du nez et de la gorge.
`
`Ne pas inhaler les vapeurs. Utiliser dans un endroit bien aéré. Éviter tout
`contact avec les yeux, la peau et les vêtements.
`
`Les conducteurs scellés dans le produit SpeedSeal doivent posséder une isolation
`de type thermoplastique ou caoutchouté homologuée.
`
`Les installateurs devraient être formés avant de fabriquer des barrières, des
`mélanges ou de mettre le produit en place. Communiquez avec Cooper Crouse-
`Hinds pour obtenir un exemplaire de la vidéo d'installation.
`
`INSTALLATION
`Figure 1 - Charte du produit SpeedSeal
`Utilisez la charte pour déterminer quelle
`grosseur de cartouche SpeedSeal vous
`devez utiliser pour des raccords
`d'étanchéité choisis.
`
`CHICO SS2 (60 ml 2 oz.)
`CHICO SS6 (180 ml 6 oz.)
`
`No de catalogue
` raccord
`
`Quantité de produit
`SpeedSeal requis
`(en ml et en onces)
`
`EYS1, EYS16, EYS11, EYS116
`EYD1, EYD16, EYD11, EYD116
`EYS2, EYS26, EYS21, EYS216
`EYD2, EYD26, EYD21, EYD216
`
`EYSX11, EYDX11
`
`EYS3, EYS36, EYS31, EYS316
`EYD3, EYD36, EYD31, EYD316
`EYSX21, EYDX21
`
`EYS41, EYS416, EYS4, EYS46
`EYD4, EYD46, EYD41, EYD416
`EYS51, EYS516, EYS5, EYS56
`EYD5, EYD56, EYD51, EYD516
`EYSX31, EYDX31
`EYSX41, EYDX41
`
`EYS61, EYS616, EYS6, EYS66
`EYD6, EYD66, EYD61, EYD616
`EYSX51, EYDX51
`
`1
`
`2
`
`3
`
`6
`
`No de
`catalogue du
`SpeedSeal
`suggéré
`
`CHICO SS2
`(cartouche de 60 ml
`ou 2 oz)
`
`CHICO SS2
`(cartouche de 60 ml
`ou 2 oz)
`
`CHICO SS6
`(cartouche de 180
`ml ou 6 oz)
`
`CHICO SS6
`(cartouche de 180
`ml ou 6 oz)
`
`IF 1457 (cid:127) 03/03
`
`© 2003, Cooper Industries, Inc.
`
`Page 4
`
`Cooper Ex. 1009
`
`

`

`La préparation des raccords d'étanchéité
`
`1.
`
`Enlevez le(s) bouchon(s) du raccord d'étanchéité EYS. Voir la figure 1.
`
`Figure 1
`
`2.
`
`3.
`
`4.
`
`5.
`
`6.
`
`7.
`
`Pour des installations verticales, utilisez la fibre Chico X pour fabriquer une
`barrière dans le bas du raccord de conduit. La barrière empêchera le produit
`SpeedSeal non figé de couler à l'extérieur de la chambre du joint. Aucune
`barrière n'est requise pour les installations horizontales à moins qu'on ne
`veuille avoir un produit gonflé dans une direction ou garder le produit à
`l'extérieur du conduit.
`
`NOTE : LA SÉPARATION DES CONDUCTEURS INDIVIDUELS N'EST PAS
`REQUISE - LE PRODUIT SPEEDSEAL SÉPARERA LES CONDUCTEURS
`QUAND IL GONFLE.
`
`Pour construire correctement une barrière dans un raccord de conduit,
`utilisez la trousse d'outils EYS ou un bâton de bois dur, pour forcer les
`conducteurs vers l'avant. Ne pas utiliser d'outils en métal.
`
`Remplissez de fibres la partie inférieure du raccord de tuyau, au-delà des
`conducteurs.
`
`Poussez les conducteurs vers l'arrière du raccord et remplissez de fibres la
`partie inférieure du raccord de tuyau, en avant des conducteurs. Ce n'est
`pas critique de séparer les conducteurs parce que le produit SpeedSeal
`gonflera et remplira l'espace autour de chaque conducteur. Cependant, une
`bonne barrière est requise pour empêcher le matériau fluide de fuir la
`chambre du joint.
`
`Ne laissez aucune parcelle de fibre coller à la paroi latérale de la chambre
`de joint ou aux conducteurs. De telles parcelles intégrées dans le produit
`d'étanchéité peuvent former des canaux de fuite. La barrière en entier devrait
`être à égalité avec le manchon intégré (bouchon de conduit).
`
`Dans les installations verticales, si le raccord d'étanchéité EYS est d'un type
`à deux orifices filetés, replacez le bouchon fileté dans l'ouverture du bas. Le
`produit d'étanchéité sera introduit par l'ouverture supérieure. Dans les
`installations horizontales, replacez le bouchon dans la plus petite ouverture
`pour introduire le produit d'étanchéité par l'ouverture la plus grande. Voir la
`figure 2.
`
`5.
`
`6.
`
`7.
`
`8.
`
`9.
`
`Enlevez la bande de ruban de la cartouche.
`
`Tirez la tige de mélange vers le haut de
`cartouche. Voir la figure 4.
`
`Figure 4
`
`Serrez la cartouche dans la zone où la bande
`de ruban a été enlevée pour déformer la feuille
`de séparation entre les deux matériaux. Voir la
`figure 5.
`
`SERRER
`
`Figure 5
`
`Poussez la tige de mélange jusqu'au fond de la cartouche (côté rouge).
`
`Mélangez rapidement à l'aide de 40 à 50 coups (un coup est un cycle
`complet d'entrée et de sortie). Durant le mélange, tenez la cartouche
`fermement et tournez dans le sens horaire pour vous assurer que le piston
`agite tout le contenu de la cartouche. NE PAS MÉLANGER PLUS DE 30
`SECONDES. LA PRESSION S'ACCUMULERA À l'INTÉRIEUR APRÈS 30
`SECONDES QUAND LE MATÉRIEL COMMENCE À GONFLER.
`
`10. Au dernier coup, poussez la tige de
`mélange jusqu'au fond (côté
`rouge), saisissez la cartouche
`fermement par le bas pour tenir le
`piston en place, dévissez
`immédiatement la tige de mélange
`et retirez-la prudemment. Voir la
`figure 6.
`
`11. Vissez la buse de coulée sur la
`cartouche où la tige de mélange
`était fixée. Voir la figure 7.
`
`POUSSEZ
`VERS LE BAS
`ET DÉVISSEZ
`
`Figure 6
`
`Figure 2
`
`Mélanger et injecter le produit SpeedSeal
`LIRE TOUTES LES INSTRUCTIONS AVANT DE MÉLANGER. LE
`1.
`PRODUIT SPEEDSEAL COMMENCE À GONFLER TRÈS RAPIDEMENT.
`ASSUREZ-VOUS DE VOUS FAMILIARISER AVEC LES INSTRUCTIONS
`DES PAGES SUIVANTES AVANT DE MÉLANGER. CECI ASSURERA UNE
`INSTALLATION CORRECTE.
`
`VISSEZ LA BUSE DE
`COULÉE DANS LA
`CARTOUCHE ICI
`
`Figure 7
`
`Assurez-vous que le produit SpeedSeal est une température entre 10 °C (50
`°F) et 30 °C (85 °F).
`
`PORTEZ DES LUNETTES DE SÉCURITÉ ET DES GANTS DE
`PROTECTION.
`
`2.
`
`3.
`
`4.
`
`12. Utilisez la tige de mélange pour pousser le piston. Injectez la quantité
`appropriée de produit d'étanchéité dans le raccord par l'orifice fileté EYS.
`Voir le tableau 1 au commencement des instructions d'installation pour la
`quantité appropriée de matériau. La cartouche est marquée par segment
`d'une once (30 ml). Voir la figure 8.
`
`SERRER
`
`Vérifiez la tige de
`mélange pour vous
`assurer qu'elle n'est ni
`trop serrée, ni trop
`desserrée. Pour faire
`cela, tenez la cartouche
`avec le bouchon de
`l'extrémité rouge vers le
`haut et serrez la
`cartouche dans la zone
`autour du piston. Cela
`maintiendra le piston en
`place. Voir la figure 3.
`Tournez légèrement
`dans le sens anti-horaire
`pour desserrer, puis
`dans le sens horaire
`pour resserrer bien en place.
`
`Figure 3
`
`Figure 8
`
`IF 1457 (cid:127) 03/03
`
`© 2003, Cooper Industries, Inc.
`
`Page 5
`
`Cooper Ex. 1009
`
`

`

`13. Replacez et serrez rapidement le bouchon de fixation étanche pour éviter
`que le produit SpeedSeal fige et obstrue les filets. Voir la figure 9.
`
`Figure 9
`
`14.
`
`Le matériau SpeedSeal devrait être utilisé immédiatement. Après une
`minute, jetez tout matériau inutilisé.
`
`15. Après avoir replacé les bouchons, attachez la plaque d'identification rouge
`avec la bande de plastique. Chaque nécessaire de modification est fourni
`avec un nombre approprié de plaques d'identification et de bandes.
`Positionnez la plaque d'identification pour une visibilité maximale.
`
`Tableau 35.1 Le nombre maximal de conducteurs qui peuvent être scellés dans un raccord
`
`Exemple d'utilisation du tableau 35.1
`Le nombre maximal de conducteurs THHN de type 4 (colonne B) permis par
`la norme UL 886 dans un raccord d'étanchéité de 1½" est 6. Les
`conducteurs THHN de type 4 (6) représentent le remplissage maximal de fils
`de 25 % ou moins pour les raccords d'étanchéité. Augmenter le diamètre du
`raccord d'étanchéité à 2" fournira de l'espace pour un remplissage de fils de
`40 %, ou neuf (9) conducteurs de type 4, et sera conforme à la norme UL
`886.
`
`Grosseur
`commerciale
`1-1/2"
`
`Grosseur du
`conducteur
`#4
`
`No max.
`permis
`pour un
`remplissage
`de 25
`6
`
`No max. permis
`pour un
`remplissage de 40%
`/ Grosseur com
`d'adjustement requis
`(9/2")
`
`Type
`THHN (Col.B)
`
`Dans notre exemple, utilisez un raccord d'étanchéité EYS6 (pour un diam. de 2", EYD, EZD ou EZS).
`Les nombres maximaux de fils qui peuvent être scellés dans un raccord sont comme suit :
`
`Grosseur
`AWG ou
`KCmII
`
`Bouchon de ½"
`(Quantite /
`Grosseur NPT)
`A
`B
`7
`11
`18
`6
`9
`16
`3
`8(13-3/4")
`14
`3
`6(10-3/4")
`12
`10 1(2-3/4")
`4(6-3/4")
`8
`1
`2(3-3/4")
`6
`1
`1
`4
`1
`1
`3
`2
`1
`1/0
`2/0
`3/0
`4/0
`250
`300
`350
`400
`500
`600
`700
`750
`800
`900
`1000
`
`Bouchon de 1"
`Bouchon de ¾"
`Bouchon de 1¼"
`(Quantite /
`(Quantite /
`(Quantite /
`Grosseur NPT)
`Grosseur NPT)
`Grosseur NPT)
`A
`B
`A
`B
`A
`B
`35
`58
`20
`33
`12
`20
`30
`47
`17
`27
`10
`16
`18
`43(69/2")
`10
`24(39/1-1/4")
`6
`15(24/1")
`15
`32(51/2")
`11(18/1") 8(9/1-1/4" 18(29/1-1/4")
`5
`13
`20(32/2")
`4
`7(11/1")
`7
`11(18/1-1/4")
`7
`11(16/1-1/2")
`2
`4(5/1")
`4
`6(9/1-1/4")
`4(6/1-1/4") 4(5/1-1/2"
`7(11/2")
`1
`2(4/1")
`2
`1
`1(2/1")
`1
`2(4/1-1/4")
`3
`4(7/2")
`1
`1
`1
`2(3/1-1/4")
`3
`3(6/2")
`1
`1
`1
`1(3/1-1/4")
`3
`3(5/2")
`1
`1
`1
`1
`1
`2(3/1-1/2")
`1
`1
`1
`1
`2(3/2")
`1
`1
`1
`1(2/1-1/2")
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`
`Col. A =
`Types RFH-2,
`RH, RHH,
`RHW, THW,
`TW, XHHW
`(AWG 14-6),
`FEPB (AWG
`6-2).
`
`Col. B -
`Types FEP,
`THHN,
`THWN, TFN,
`PF, PGF,
`XHHW, (AWG
`4-2000
`MCM), FEPB
`(AWG 14-8).
`
`Bouchon de 1½"
`(Quantite /
`Grosseur NPT)
`A
`B
`49
`80
`41
`64
`25
`58(94/2")
`21
`43(70/2")
`17(18/2")
`27(44/2")
`9
`16(22/2")
`6
`9(15/2")
`5
`6(9/2")
`4
`5(8/2")
`3(4/2")
`4(7/2")
`3
`3(5/2")
`2
`2(4/2")
`1
`2(3/2")
`1
`1(3/2")
`1
`1(2/2")
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`
`Bouchon de 2"
`(Quantite /
`Grosseur NPT)
`A
`B
`80
`131
`68
`106
`41
`96(154/3")
`34(35/2-1/2")
`71(114/3")
`29
`45(73/3")
`16
`26(36/2-1/2")
`10(11/2-1/2")
`16(26/3")
`8
`9(16/3")
`7
`8(13/3")
`6
`7(11/3")
`4(5/2-1/2")
`5(8/3")
`4
`4(7/3")
`3
`3(6/3")
`3
`3(5/3")
`2
`2(4/3")
`1
`2(3/2-1/2")
`1
`1(3/1-1/2")
`1
`1(2/1-1/2")
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`1
`
`Tous les énoncés, renseignements techniques et recommandations contenus dans ce document sont basés sur des renseignements et des tests que
`nous jugeons dignes de confiance. La précision ou la complétude de ces renseignements ou autres ne sont cependant pas garanties. En accord avec
`les conditions de ventes de Crouse-Hinds, et parce que les conditions d'utilisation ne sont pas sous notre contrôle, l'acheteur doit déterminer
`l'applicabilité du produit pour son utilisation prévue et assumer tous les risques et responsabilités de quelque nature que ce soit qui s'y rattachent.
`
`Cooper Industries Inc.
`Division Crouse-Hinds
`B.P. 4999. 13221, Syracuse, New York
`© 2003, Cooper Industries, Inc.
`
`IF 1457
`Révision 1
`États-Unis. Nouveau 03/03
`
`Cooper Ex. 1009
`
`

`

`Compuesto CHICO® SpeedSeal™
`Compuesto Sellante de Acción Rápida
`Paquete para Modificar Accesorios para Sello
`Para uso con accesorios para sello
`EYS de Crouse-Hinds
`Información para Instalación y Mantenimiento.
`CONSERVE ESTAS INSTRUCCIONES PARA FUTURAS REFERENCIAS
`
`IF 1457
`
`PRECAUCION
`El compuesto CHICO SpeedSeal (Sello rápido) esta hecho para utilizarse
`únicamente con accesorios para sello del tipo EYS de Cooper Crouse-Hinds
`para las medidas comerciales de ½" a 2" (13 mm a 50.8 mm). El compuesto
`SpeedSeal (Sello rápido) es adecuado para Areas Peligrosas Clase I,
`División 1 y 2, Grupos C & D y Clase II, División 1 y 2, Grupos E, F & G
`únicamente, aún cuando se utilice un accesorio clasificado para Grupo B.
`
`PRECAUCION
`La temperatura del compuesto SpeedSeal (Sello rápido) debe estar entre 50°F
`(10°C) y 85°F (29°C) antes de ser mezclado. Los accesorios para sello deben
`estar a una temperatura superior a los 40°F (4°C). El compuesto SpeedSeal
`(Sello rápido) se expanderá hasta 4 veces su volumen original cuando ha
`curado.
`
`APLICACIÓN
`El Código Eléctrico Nacional (NEC por sus siglas en inglés) en el artículo 501,
`Sección 501-5, requiere que los sellos sean instalados en lugares específicos en
`áreas clasificadas Clase I, División 1 y 2. Esto es para minimizar el paso de gases y
`vapores y previene el paso de las flamas a través de una porción de la tubería
`conduit a otra de una instalación eléctrica.
`
`Mientras no es un requerimiento del código, es considerada una buena práctica el
`seccionar los tramos de tubería conduit que son largos mediante la inserción de
`sellos a distancias no mayores de 50 a 100 pies (15 a 30 mts), dependiendo del
`tamaño de la tubería conduit, para minimizar los efectos de "presión en cascada".
`
`EL NEC en la Sección 502-5 requiere de sellos en lugares Clase II bajo ciertas
`condiciones. Los accesorios para sello Cooper Crouse-hinds pueden ser utilizados
`para cumplir estos requerimientos.
`
`Los sellos para tubería conduit no están destinados para prevenir el paso de
`líquidos, gases o vapores a una presión diferencial continua a traves del sello. Aún
`con diferencias de presión a traves del sello equivalen a unas pocas pulgadas de
`agua, esto puede ser un paso lento de gas o vapor a través de un sello y a través
`de los conductores pasa a través del sello.
`
`Los accesorios de Cooper Crouse- Hinds están listados por Underwriters
`Laboratories, Inc. (UL), para utilizarse en áreas peligrosas Clase I y Clase II con el
`compuesto sellador Chico A y la fibra Chico X. Alternativamente, los accesorios
`para sello del tipo EYS de Cooper Crouse-Hinds están también listados por UL
`para utilizarse en áreas peligrosas Clase I, División 1 y 2, Grupos C & D y Clase II,
`División 1 y 2, Grupos E, F & G con el compuesto sellador SpeedSeal de Cooper
`Crouse-Hinds.
`
`El compuesto CHICO SpeedSeal (Sello rápido) puede utilizarse para sellar ambas
`instalaciones horizontales y verticales. Puede utilizarse con los accesorios para
`sello tipo EYS de las medidas ½ " a 2", en áreas peligrosas Clase I, División 1 y 2,
`Grupos C y D y Clase II, División 1 y 2, Grupos E, F & G. El compuesto SpeedSeal
`(Sello rápido) debe utilizarse con la fibra Chico X en instalaciones verticales. La
`fibra Chico X es usada para crear un tapón para prevenir que el material del
`SpeedSeal se derrame en la tubería antes de que éste se endurezca. El
`taponamiento no se requiere en tramos de tubería verticales.
`
`Sin embargo, si quieres prevenir que el compuesto sellador se exoanda hacia la
`tubería, utiliza la fibra Chico X para crear un tapón en el tope integrado que tienen
`los accesorios para sello.
`
`El compuesto sellador SpeedSeal, cuando es apropiadamente mezclado, comienza
`a solidificar en aproximadamente 4 minutos a 70°F (21°C) o 10 minutos a 40°F
`(4°C) y se convierte en una densa, masa sólida a la cual el agua no le afecta, los
`productos a base de petróleo no la atacan y no la ablanda el calor. Se endurecerá
`en 20 minutos y soportará, con un amplio factor de seguridad, la presión generada
`de la explosión de un gas o vapor.
`
`PRECAUCION
`
`Utilize la protección apropiada para sus ojos y los guantes de plástico
`protectores cuando mezcle e inyecte el compuesto SpeedSeal (Sello rápido)
`
`AVERTISSEMENT
`El contenido desarrollará una presión interna después de mezclarse. Retire
`la barra mezcladora inmediatamente después de mezclar para prevenir que
`la presión aumente y produzca una repentina explosión que podría
`lesionarlo.
`
`Contiene isocianato - puede ser sensible a la piel y el olfato. Puede causar
`irritación de ojos, piel, nariz y garganta.
`
`No respire los vapores. Utilizese en lugares con una adecuada ventilación.
`Evite el contacto con los ojos, piel y ropa.
`
`Los conductores sellados en el compuesto SpeedSeal deben contar con un tipo de
`aislamiento termoplástico o neopreno aprobado. Los instaladores deben estar
`capacitados antes de hacer el taponeo, mezclado y vaciado del compuesto. Llame a
`Cooper Crouse-Hinds para obtener una copia del video de instalación.
`
`INSTALACIÓN
`Figura 1 -
`Tabla del Compuesto SpeedSeal
`Utilice la tabla para determinar el tamaño
`de cartucho SpeedSeal a usar para el
`accesorio de sellado seleccionado.
`
`CHICO SS2 (60 ml 2 oz.)
`CHICO SS6 (180 ml 6 oz.)
`
`Número de
`Catalogo
`
`Cantidad requerida
`de material de
`SpeedSeal en onzas)
`
`EYS1, EYS16, EYS11, EYS116
`EYD1, EYD16, EYD11, EYD116
`EYS2, EYS26, EYS21, EYS216
`EYD2, EYD26, EYD21, EYD216
`
`EYSX11, EYDX11
`
`EYS3, EYS36, EYS31, EYS316
`EYD3, EYD36, EYD31, EYD316
`EYSX21, EYD

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket