`
`
`
`
`
`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`IN THE UNITED STATES PATENT AND TRADEMARK OFFICE
`____________________________
`BEFORE THE PATENT TRIAL AND APPEAL BOARD
`____________________________
`
`WILLIAM SYKES,
`Petitioner,
`
`v.
`
`SMART VENT PRODUCTS, INC.,
`Patent Owner
`____________________________
`
`Case IPR2019-01061
`Patent 9,909,302
`____________________________
`
`
`PETITIONER’S REQUEST FOR RECONSIDERATION
`
`COMES NOW William Sykes (“Petitioner”) and for his Request for
`
`Reconsideration states as follows.
`
`A.
`
`Background
`
`Petitioner filed a Petition for Inter Partes review of U.S. Patent No.
`
`9,909,302. On October 21, 2019, the Board issued a Decision denying
`
`institution of Inter Partes Review. Petitioner respectfully submits this
`
`Request for Reconsideration in response.
`
`1
`
`
`
`
`
`
`
`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`B. Claims 1 and 12 and their dependent Claims (3 and 18)
`
`In response to the Board’s Decision of October 21, 2019, Paper 11,
`
`Petitioner respectfully withdraws his request for Inter Partes Review of
`
`Claims 1, 3, 12, and 18.
`
`C. Denial of Institution of Inter Partes Review of Claims 7 and
`
`11.
`
`In response to the Board’s Decision of October 21, 2019, Paper 11,
`
`Petitioner respectfully requests that the Board reconsider its Denial of
`
`institution of Inter Partes Review. In particular, Petitioner respectfully
`
`submits that the Board overlooked the incorporation of materials by
`
`reference related to the claimed limitation of “0.5-5 pounds per square inch”
`
`in Claim 7 and its dependent Claim 11, and how those materials would
`
`provide one skilled in the art with prior art anticipation of the claimed
`
`limitation.
`
`D. Argument
`
`The Board has denied institution of an Inter Partes review of Claims 7
`
`and 11 of the ‘302 patent.
`
`Claim 7 of the ‘302 patent teaches the uncoupling of the panel from
`
`the frame by applying 0.5-5.0 pounds per square inch of force. The Board
`
`has stated that “Petitioner’s evidence is insufficient to demonstrate that
`2
`
`
`
`
`
`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`
`Shook discloses, or the combination of Shook and Malitsky teach or suggest,
`
`uncoupling the panel from the frame by applying 0.5-5.0 pounds per square
`
`inch of pressure on either side of the panel. Instead, the evidence to which
`
`Petitioner directs us merely discloses that Shook’s shutter 30 moves about a
`
`swing arc in response to a floodwater pressure differential in or across duct
`
`15. . . [and] [t]he cited portion of Shook is silent as to the amount of applied
`
`pressure required to uncouple the panel from the frame . . .” Paper 11, page
`
`13.
`
`Despite that finding, however, Petitioner respectfully submits that the
`
`range limitation in Claim 7 for uncoupling the panel from the frame is
`
`incorporated by reference in Shook an Malitsky, as well as within the ‘302
`
`patent, and more importantly is well known to those skilled in the art; that
`
`limitation would be well known by one reasonably skilled in the art of
`
`designing and building flood vents for crawl spaces, as those disclosed in the
`
`‘302 patent.
`
`Incorporation by reference provides anticipatory prior art. “To
`
`incorporate material by reference, the host document must identify with
`
`particularity what specific material it incorporates and clearly indicate
`
`where that material is found in the various documents.” Advanced System
`
`Display Sys., Inc. v. Kent State Univ., 212 F.3d 1272, 1282 (Fed. Cir. 2000).
`3
`
`
`
`
`
`
`
`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`And when making that determination, the standard that applies is that of
`
`“one reasonably skilled in the art.” Id. At 1283.
`
`Flood vents are designed to be compliant with government
`
`regulations, specifically those promulgated by the Federal Emergency
`
`Management Agency. The ‘302 patent, Shook, and Malitsky all
`
`acknowledge this and incorporate that knowledge in the art by reference.
`
`The ‘302 patent itself specifically cites to, in OTHER
`
`PUBLICATIONS:
`
`FEMA, Openings in Foundation Walls and Walls of Enclosures,
`
`Technical Bulletin, Aug. 1, 2008, and
`
`FEMA, Non-Residential Floodproofing, Technical Bulletin, Apr. 3,
`
`1993.
`
`Shook directly teaches that FEMA requirements provide the impetus
`
`for the inventive steps taken in designing flood vents:
`
`“To eliminate or at least reduce damage due to flooding,
`several building code entities as well as the federal government
`have developed rules and regulations requiring structures
`with enclosed spaces located below defined flood plain
`levels to include automatic equalization of interior and exterior
`hydrostatic pressure caused by floodwaters. The rules and
`regulations require structures to be designed and built to
`allow floodwaters to move in and out of a structure freely. The
`Federal Emergency Management Agency (FEMA) requires
`compliance with FEMA Technical Bulletin 1-93. Other governmental
`agencies required compliance with the International
`4
`
`
`
`
`
`
`
`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`Building Code and/or ASME 24-05 and 24-98.”
`
`Shook, Ex. 1002, 1:13-24.
`
`And Malitksy acknowledges the same state of the art:
`
`“With the advent of major flooding issues throughout
`many areas of the United States, national agencies such as
`Federal Emergency Management Administration (FEMA)
`and National Flood Insurance Program (NFIP), a flood insurance
`division of FEMA, have set out to that building codes
`mandate that new and existing structures install flood and air
`ventilation systems within the foundations.
`To date, within FEMA defined flood zones, in order
`to obtain building permits and flood insurance for structures,
`whether newly constructed or substantially renovated that
`incorporate crawl spaces and/or unfinished basements,
`FEMA and the NFIP now require the installation of flood
`vents.”
`
`Malitksy, Ex. 1003, 1:[0003]-[0004].
`
`Malitksy further states that the Malitsky invention was specifically
`
`designed to:
`
`“comply with, or be adaptable to, the following standards, including
`but not limited to:
`“FEMA/FIA Technical Bulletin TB 1-93 "Engineered
`Opening Requirements";
`American Society of Construction Engineers
`(ASCE) 24-05 "Flood Resistant Design and Construction";
`and
`FEMA National Flood Insurance Program Regulations
`44 CFR 60.3”
`
`Malitsky, Ex. 1003, 1:[0016]-[0019].
`
`5
`
`
`
`
`
`
`
`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`The state of the art for flood vents and flood vent designs is therefore
`
`disclosed, and incorporated by reference, in the ‘302 patent, Shook, and
`
`Malitsky. Further, each of the ‘302 patent, Shook, and Malitsky specifically
`
`refer to that state of the art and those governmentally-mandated
`
`requirements.
`
`And that state of the art, well known by those skilled in the art, is
`
`those guidelines and restrictions promulgated by FEMA in its publications
`
`related to flood mitigation and the use of flood vents. Those guidelines and
`
`regulations of FEMA are materials that the Board may take judicial notice
`
`of as public specifically allowable under F.R.E. 201. See 37 CFR § 42.62.
`
`The public records provided by FEMA related to the design and state of the
`
`art related to flood vents is therefore properly before the Board. And, as
`
`noted above, the ‘302 patent as well as Shook and Malitsky all acknowledge
`
`and incorporate by reference FEMA’s standards and guidance for flood
`
`vents and flood vent design.
`
`FEMA provides well-known calculations for determining hydrostatic
`
`loads as a result of standing water and in particular for floodwater openings.
`
`See, e.g., https://www.fema.gov/media-library-data/20130726-1518-20490-
`
`6246/05_fema_p550_ch3.pdf at 3.3 (Hydrostatic Loads). Those guidelines
`
`provide that:
`
`6
`
`
`
`
`
`
`
`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`Lateral hydrostatic force is calculated by the following: fstat = ½ γ ds2
`
`Where
`
`fstat = Hydrostatic force per unit width (lb/ft) resulting from flooding
`
`against vertical element;
`
`γ = Specific weight of water (62.4 lb/ft3 for freshwater and 64 lb/ft3
`
`for saltwater).
`
`The conversion of lbs/ft to pounds per square inch provides that the
`
`pressure, at one foot of water depth on a vertical surface is 0.434 pounds per
`
`square inch. In order to comply with FEMA requirements, therefore, any
`
`flood vent design must be able to allow the equalization of hydrostatic
`
`pressure on either side of the flood vent at or close to the FEMA-mandated
`
`limits. It would be obvious, therefore, to one skilled in the art to provide a
`
`flood vent that opens (or releases) upon a pressure differential between the
`
`interior and exterior of a crawl space that meets or exceeds the pressure
`
`differential at or exceeding the minimum requirements defined by FEMA.
`
`FEMA dictates, and dictated prior to the filing of the ‘302
`
`application, that flood vents that that comply with FEMA requirements
`
`maintain a maximum of one foot of difference in height between the water
`
`depth in an enclosed crawl space and the exterior of a structure. FEMA has
`
`7
`
`
`
`
`
`
`
`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`dictated that a one (1) foot differential is critical to the guidelines for
`
`providing flood protection:
`
`“The purpose of this requirement is to satisfy the performance
`
`expectation that the difference in water levels between the interior and
`
`exterior will not exceed 1 foot as water begins to rise and as floodwaters
`
`recede from the site.” FEMA TB-1, p. 14, https://www.fema.gov/media-
`
`library-data/20130726-1502-20490-9949/fema_tb_1__1_.pdf.
`
`It was well understood by those skilled in the field of flood vents,
`
`therefore, that a flood vent must be able to equilibrate pressure on either
`
`side of a flood vent once water pressure reached a certain value. A flood
`
`vent, under FEMA guidelines, must be able to allow the flow of water to
`
`limit the water height differential on either side of the flood vent to the
`
`FEMA-restricted guideline of one foot.
`
`The claimed limitations of Claim 7 and dependent Claim 11,
`
`therefore, are not just well known in the art, they are required by limitations
`
`set by FEMA and well understood by those designing and producing flood
`
`vents. The FEMA requirements and limitations are not just required, they
`
`are (and were) well known in the art, and understood by those skilled in the
`
`art to apply to flood vents designed to comply with FEMA guidelines as
`
`those disclosed in the ‘302 application admittedly must.
`8
`
`
`
`
`
`
`
`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`In sum, FEMA requirements demand that crawl space flood vents
`
`limit the height between the interior and exterior of a crawl space to one
`
`foot of height differential. It was well known in the art that those
`
`limitations applied to crawl space vents, and each of the ‘302, Shook, and
`
`Malitsky references clearly incorporate by reference those limitations.
`
`Those limitation are therefore anticipatory, and warrant the institution of an
`
`Inter Partes review of Claims 7 and 11 of the ‘302 patent.
`
`E.
`
`CONCLUSION
`
`For the reasons stated above, Petitioner respectfully requests that the
`
`Board reconsider its denial of October 21, 2019, and institute an Inter Partes
`
`review of Claims 7 and 11 of U.S. Pat. No. 9,909,302.
`
`Dated: November 20, 2019
`
`
`
`
`
`
`
`
`
`Respectfully submitted,
`/Duncan G. Byers/
`Duncan G. Byers
`Registration No. 50,707
`Attorney for William Sykes
`Patten, Wornom, Hatten & Diamonstein
`12350 Jefferson Ave.
`Suite 300
`Newport News, VA 23602
`Telephone: (757) 223.4474
`Fax: (757) 249.1627
`
`9
`
`
`
`
`
`
`
`
`
`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`CERTIFICATE OF SERVICE
`
`I hereby certify that this foregoing pleading has been filed electronically via
`
`the PTAB electronic filing system, and that I have also served, electronically, a
`
`copy of the foregoing via electronic mail to:
`
`Mark D. Passler, Esq.
`Brice Dumais, Esq.
`Akerman LLP
`777 South Flagler Drive
`Suite 1100, West Tower
`West Palm Beach, FL 33401
`ip@ackerman.com
`Brice.dumais@akerman.com
`
`
`
`10
`
`
`
`
`
`