throbber

`
`
`
`
`
`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`IN THE UNITED STATES PATENT AND TRADEMARK OFFICE
`____________________________
`BEFORE THE PATENT TRIAL AND APPEAL BOARD
`____________________________
`
`WILLIAM SYKES,
`Petitioner,
`
`v.
`
`SMART VENT PRODUCTS, INC.,
`Patent Owner
`____________________________
`
`Case IPR2019-01061
`Patent 9,909,302
`____________________________
`
`
`PETITIONER’S REQUEST FOR RECONSIDERATION
`
`COMES NOW William Sykes (“Petitioner”) and for his Request for
`
`Reconsideration states as follows.
`
`A.
`
`Background
`
`Petitioner filed a Petition for Inter Partes review of U.S. Patent No.
`
`9,909,302. On October 21, 2019, the Board issued a Decision denying
`
`institution of Inter Partes Review. Petitioner respectfully submits this
`
`Request for Reconsideration in response.
`
`1
`
`
`
`
`
`

`

`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`B. Claims 1 and 12 and their dependent Claims (3 and 18)
`
`In response to the Board’s Decision of October 21, 2019, Paper 11,
`
`Petitioner respectfully withdraws his request for Inter Partes Review of
`
`Claims 1, 3, 12, and 18.
`
`C. Denial of Institution of Inter Partes Review of Claims 7 and
`
`11.
`
`In response to the Board’s Decision of October 21, 2019, Paper 11,
`
`Petitioner respectfully requests that the Board reconsider its Denial of
`
`institution of Inter Partes Review. In particular, Petitioner respectfully
`
`submits that the Board overlooked the incorporation of materials by
`
`reference related to the claimed limitation of “0.5-5 pounds per square inch”
`
`in Claim 7 and its dependent Claim 11, and how those materials would
`
`provide one skilled in the art with prior art anticipation of the claimed
`
`limitation.
`
`D. Argument
`
`The Board has denied institution of an Inter Partes review of Claims 7
`
`and 11 of the ‘302 patent.
`
`Claim 7 of the ‘302 patent teaches the uncoupling of the panel from
`
`the frame by applying 0.5-5.0 pounds per square inch of force. The Board
`
`has stated that “Petitioner’s evidence is insufficient to demonstrate that
`2
`
`
`
`
`
`

`

`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`
`Shook discloses, or the combination of Shook and Malitsky teach or suggest,
`
`uncoupling the panel from the frame by applying 0.5-5.0 pounds per square
`
`inch of pressure on either side of the panel. Instead, the evidence to which
`
`Petitioner directs us merely discloses that Shook’s shutter 30 moves about a
`
`swing arc in response to a floodwater pressure differential in or across duct
`
`15. . . [and] [t]he cited portion of Shook is silent as to the amount of applied
`
`pressure required to uncouple the panel from the frame . . .” Paper 11, page
`
`13.
`
`Despite that finding, however, Petitioner respectfully submits that the
`
`range limitation in Claim 7 for uncoupling the panel from the frame is
`
`incorporated by reference in Shook an Malitsky, as well as within the ‘302
`
`patent, and more importantly is well known to those skilled in the art; that
`
`limitation would be well known by one reasonably skilled in the art of
`
`designing and building flood vents for crawl spaces, as those disclosed in the
`
`‘302 patent.
`
`Incorporation by reference provides anticipatory prior art. “To
`
`incorporate material by reference, the host document must identify with
`
`particularity what specific material it incorporates and clearly indicate
`
`where that material is found in the various documents.” Advanced System
`
`Display Sys., Inc. v. Kent State Univ., 212 F.3d 1272, 1282 (Fed. Cir. 2000).
`3
`
`
`
`
`
`

`

`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`And when making that determination, the standard that applies is that of
`
`“one reasonably skilled in the art.” Id. At 1283.
`
`Flood vents are designed to be compliant with government
`
`regulations, specifically those promulgated by the Federal Emergency
`
`Management Agency. The ‘302 patent, Shook, and Malitsky all
`
`acknowledge this and incorporate that knowledge in the art by reference.
`
`The ‘302 patent itself specifically cites to, in OTHER
`
`PUBLICATIONS:
`
`FEMA, Openings in Foundation Walls and Walls of Enclosures,
`
`Technical Bulletin, Aug. 1, 2008, and
`
`FEMA, Non-Residential Floodproofing, Technical Bulletin, Apr. 3,
`
`1993.
`
`Shook directly teaches that FEMA requirements provide the impetus
`
`for the inventive steps taken in designing flood vents:
`
`“To eliminate or at least reduce damage due to flooding,
`several building code entities as well as the federal government
`have developed rules and regulations requiring structures
`with enclosed spaces located below defined flood plain
`levels to include automatic equalization of interior and exterior
`hydrostatic pressure caused by floodwaters. The rules and
`regulations require structures to be designed and built to
`allow floodwaters to move in and out of a structure freely. The
`Federal Emergency Management Agency (FEMA) requires
`compliance with FEMA Technical Bulletin 1-93. Other governmental
`agencies required compliance with the International
`4
`
`
`
`
`
`

`

`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`Building Code and/or ASME 24-05 and 24-98.”
`
`Shook, Ex. 1002, 1:13-24.
`
`And Malitksy acknowledges the same state of the art:
`
`“With the advent of major flooding issues throughout
`many areas of the United States, national agencies such as
`Federal Emergency Management Administration (FEMA)
`and National Flood Insurance Program (NFIP), a flood insurance
`division of FEMA, have set out to that building codes
`mandate that new and existing structures install flood and air
`ventilation systems within the foundations.
`To date, within FEMA defined flood zones, in order
`to obtain building permits and flood insurance for structures,
`whether newly constructed or substantially renovated that
`incorporate crawl spaces and/or unfinished basements,
`FEMA and the NFIP now require the installation of flood
`vents.”
`
`Malitksy, Ex. 1003, 1:[0003]-[0004].
`
`Malitksy further states that the Malitsky invention was specifically
`
`designed to:
`
`“comply with, or be adaptable to, the following standards, including
`but not limited to:
`“FEMA/FIA Technical Bulletin TB 1-93 "Engineered
`Opening Requirements";
`American Society of Construction Engineers
`(ASCE) 24-05 "Flood Resistant Design and Construction";
`and
`FEMA National Flood Insurance Program Regulations
`44 CFR 60.3”
`
`Malitsky, Ex. 1003, 1:[0016]-[0019].
`
`5
`
`
`
`
`
`

`

`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`The state of the art for flood vents and flood vent designs is therefore
`
`disclosed, and incorporated by reference, in the ‘302 patent, Shook, and
`
`Malitsky. Further, each of the ‘302 patent, Shook, and Malitsky specifically
`
`refer to that state of the art and those governmentally-mandated
`
`requirements.
`
`And that state of the art, well known by those skilled in the art, is
`
`those guidelines and restrictions promulgated by FEMA in its publications
`
`related to flood mitigation and the use of flood vents. Those guidelines and
`
`regulations of FEMA are materials that the Board may take judicial notice
`
`of as public specifically allowable under F.R.E. 201. See 37 CFR § 42.62.
`
`The public records provided by FEMA related to the design and state of the
`
`art related to flood vents is therefore properly before the Board. And, as
`
`noted above, the ‘302 patent as well as Shook and Malitsky all acknowledge
`
`and incorporate by reference FEMA’s standards and guidance for flood
`
`vents and flood vent design.
`
`FEMA provides well-known calculations for determining hydrostatic
`
`loads as a result of standing water and in particular for floodwater openings.
`
`See, e.g., https://www.fema.gov/media-library-data/20130726-1518-20490-
`
`6246/05_fema_p550_ch3.pdf at 3.3 (Hydrostatic Loads). Those guidelines
`
`provide that:
`
`6
`
`
`
`
`
`

`

`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`Lateral hydrostatic force is calculated by the following: fstat = ½ γ ds2
`
`Where
`
`fstat = Hydrostatic force per unit width (lb/ft) resulting from flooding
`
`against vertical element;
`
`γ = Specific weight of water (62.4 lb/ft3 for freshwater and 64 lb/ft3
`
`for saltwater).
`
`The conversion of lbs/ft to pounds per square inch provides that the
`
`pressure, at one foot of water depth on a vertical surface is 0.434 pounds per
`
`square inch. In order to comply with FEMA requirements, therefore, any
`
`flood vent design must be able to allow the equalization of hydrostatic
`
`pressure on either side of the flood vent at or close to the FEMA-mandated
`
`limits. It would be obvious, therefore, to one skilled in the art to provide a
`
`flood vent that opens (or releases) upon a pressure differential between the
`
`interior and exterior of a crawl space that meets or exceeds the pressure
`
`differential at or exceeding the minimum requirements defined by FEMA.
`
`FEMA dictates, and dictated prior to the filing of the ‘302
`
`application, that flood vents that that comply with FEMA requirements
`
`maintain a maximum of one foot of difference in height between the water
`
`depth in an enclosed crawl space and the exterior of a structure. FEMA has
`
`7
`
`
`
`
`
`

`

`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`dictated that a one (1) foot differential is critical to the guidelines for
`
`providing flood protection:
`
`“The purpose of this requirement is to satisfy the performance
`
`expectation that the difference in water levels between the interior and
`
`exterior will not exceed 1 foot as water begins to rise and as floodwaters
`
`recede from the site.” FEMA TB-1, p. 14, https://www.fema.gov/media-
`
`library-data/20130726-1502-20490-9949/fema_tb_1__1_.pdf.
`
`It was well understood by those skilled in the field of flood vents,
`
`therefore, that a flood vent must be able to equilibrate pressure on either
`
`side of a flood vent once water pressure reached a certain value. A flood
`
`vent, under FEMA guidelines, must be able to allow the flow of water to
`
`limit the water height differential on either side of the flood vent to the
`
`FEMA-restricted guideline of one foot.
`
`The claimed limitations of Claim 7 and dependent Claim 11,
`
`therefore, are not just well known in the art, they are required by limitations
`
`set by FEMA and well understood by those designing and producing flood
`
`vents. The FEMA requirements and limitations are not just required, they
`
`are (and were) well known in the art, and understood by those skilled in the
`
`art to apply to flood vents designed to comply with FEMA guidelines as
`
`those disclosed in the ‘302 application admittedly must.
`8
`
`
`
`
`
`

`

`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`In sum, FEMA requirements demand that crawl space flood vents
`
`limit the height between the interior and exterior of a crawl space to one
`
`foot of height differential. It was well known in the art that those
`
`limitations applied to crawl space vents, and each of the ‘302, Shook, and
`
`Malitsky references clearly incorporate by reference those limitations.
`
`Those limitation are therefore anticipatory, and warrant the institution of an
`
`Inter Partes review of Claims 7 and 11 of the ‘302 patent.
`
`E.
`
`CONCLUSION
`
`For the reasons stated above, Petitioner respectfully requests that the
`
`Board reconsider its denial of October 21, 2019, and institute an Inter Partes
`
`review of Claims 7 and 11 of U.S. Pat. No. 9,909,302.
`
`Dated: November 20, 2019
`
`
`
`
`
`
`
`
`
`Respectfully submitted,
`/Duncan G. Byers/
`Duncan G. Byers
`Registration No. 50,707
`Attorney for William Sykes
`Patten, Wornom, Hatten & Diamonstein
`12350 Jefferson Ave.
`Suite 300
`Newport News, VA 23602
`Telephone: (757) 223.4474
`Fax: (757) 249.1627
`
`9
`
`
`
`
`
`

`

`
`
`
`
`
`
` Request for Reconsideration
` U.S. Pat. No. 9,909,302 Docket No. 62354/00000
`
`
`CERTIFICATE OF SERVICE
`
`I hereby certify that this foregoing pleading has been filed electronically via
`
`the PTAB electronic filing system, and that I have also served, electronically, a
`
`copy of the foregoing via electronic mail to:
`
`Mark D. Passler, Esq.
`Brice Dumais, Esq.
`Akerman LLP
`777 South Flagler Drive
`Suite 1100, West Tower
`West Palm Beach, FL 33401
`ip@ackerman.com
`Brice.dumais@akerman.com
`
`
`
`10
`
`
`
`
`
`

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket