throbber
Copyright 2046 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and download on 70/18/2015 to VoltServerfor designated user Stephen Eaves. No other reproduction or transmission in any
`form permitted without written permission of NFPA, Farinquiries or to report unauthorized use, contact licensing@nfpa.org.
`
`ARTICLE 430 — MOTORS, MOTORCIRCUITS, AND CONTROLLERS
`
`430.75
`
`(lL) Separate Overcurrent Protection, Where the motor
`branch-circuit short-circuit and ground-fault protective device
`does not provide protection in accordance with 430.72(B) (2),
`separate overcurrent protection shall be provided. The over-
`current protection shall not exceed the values specified in
`Column A of Table 430.72(B).
`
`(2) Branch-Circnit Overcurrent Protective Device. Conduc-
`tors shall be permitted to be protected by the motor branch-
`circuit short-circuit and ground-fault protective device and
`shall require only short-circuit and ground-fault protection.
`Where the conductors do not extend beyond the motor
`control equipment enclosure,
`the rating of the protective
`device(s) shall not exceed the value specified in Column B of
`Table 430.72(B). Where the conductors extend beyond the
`motor control equipment enclosure, the rating of the protec-
`tive device(s) shall not exceed the value specified in Column G
`of Table 430.72({B).
`
`(C} Control Circuit Transformer. Where a motor control
`circuit transformeris provided, the transformer shall be protec-
`ted in accordance with 430.72(C) (13, (C)¢2), (C)(3), (C) (4),
`or (C){5).
`
`Exception: Overcurrent protection shall be omitted where the opening of
`the control circuit would create a hazard as, for example,
`the controt
`circuit ofa fire pump motor and thelike,
`
`{1) Compliance with Article 725. Where the transformer
`supplies a Class | powerlimited circuit, Class 2, or Class 3
`remote-control circuit complying with the requirements of Arti-
`cle 725, protection shall comply with Article 725.
`
`(2) Compliance with Article 450. Protection shall be permit-
`ted to be provided in accordance with 450.3.
`
`(3) Less Than 56 Volt-Amperes. Control circuit transformers
`rated less than 50 volt-amperes (VA) and that are an integral
`part of the motor controler and located within the motor
`controller enclosure shall be permitted to be protected by
`primary overcurrent devices,
`impedance limiting means, or
`other inherent protective means.
`
`(4) Primary Less Than 2 Amperes. Where the control circuit
`transformer rated primary current is less than 2 amperes, an
`
`overcurrent device rated orset at not more than 500 percent of
`the rated primary current shall be permitted in the primary
`circuit.
`
`(5) Other Means. Protection shall be permitted to be provi-
`ded by other approved means.
`
`from Physical Damage.
`430.73 Protection of Conductors
`Where damage to a motor contro] circuit would constitute a
`hazard, ali conductors of such a remote motor control circuit
`that are outside the control deviceitself shall be instailed in a
`
`raceway or be otherwise protected from physical damage.
`
`430.74 Electrical Arrangement of Gontrol Circuits. Where
`one conductor of the motor control circuit is grounded, the
`motor control circuit shall be arranged so that a ground fault
`in the control circuit remote from the motor controller will
`
`(1) not start the motor and (2) not bypass manually operated
`shutdown devices or automatic safety shutdown devices.
`430.75 Disconnection.
`
`(A) General. Motor control circuits shall be arranged so that
`they will be disconnected from all sources of supply when the
`disconnecting means is in the open position. The disconnect:
`ing meansshail be permitted to consist of two or more separate
`devices, one of which disconnects the motor and the controller
`from the source(s) of power supply for the motor, and the
`other(s}, the motor contro! circuit(s) from its power supply.
`Whereseparate devices are used, they shall be located immedi-
`ately adjacent to each other.
`
`Exception. No. 1: Where more than 12 motor control circuit conductors
`are required to be disconnected, the disconnecting means shall be permit.
`ted to be located other than immediately adjacent to each other where all
`of thefollowing conditions are complied with:
`(a} Access te energized parts is limited to qualified persons in
`accordance with Part XH of this article.
`(i) A warning signis permanently located on the outside of eack
`equipment enclosure door or cover permitting access to the live parts in
`the motor control circuii(s), warning that motor confrol circuit discon-
`necting means are remotely located and specifying the location and
`identification of each disconnect. Where energized parts are not in an
`equipment enclosure as permitted by 430.232 and 430.233, an addi-
`
`‘Table 430.72(B) Maximum Rating of Overcurrent Protective Device in Amperes
`
`Control Circuit
`
`Column A Separate Protection
`Provided
`Aluminum or
`
`
`Protection Provided by Motor Branch-Circuit Protective Device(s)
`Colum B
`Conductors Within
`Enclosure
`Aluminum or
`
`Column C Conductors Extend Beyond
`Enclosure
`Aluminum or
`
`Conductor Size
`Copper-Clad
`Copper-Clad
`Copper-Clad
`
`(AWG)
`Copper
`Aluminum
`Copper
`Aluminum
`Copper
`Aluminum
`18
`7
`—
`25
`—_
`7
`noe
`16
`10
`—
`40
`—
`10
`—
`14
`(Note 1}
`_
`166
`—
`45
`—
`12
`(Note 1}
`(Note 1}
`120
`106
`60
`45
`10
`(Note 1}
`(Note 1}
`166
`140
`90
`75
`Larger than 19
`(Note 1}
`(Note 1}
`(Note 2)
`(Note 2)
`(Note 3)
`(Note 3)
`Notes:
`1. Value specified in 310.15 as applicable,
`2, 400 percent of value specified in Table 310.15(B) (17) for 66°C conductors.
`3. 300 percent of value specified in Table 310.15(B) (16) for 66°C conductors.
`
`Page 314 of 881
`
`VOLTSERVER EXHIBIT 1019 (part 2 of 3)
`
`

`

`Copyright 2016 National Fire Profection Association (NFPA). Licensed, by agreement, for individual use end download on 10/18/2016 te VoltGerver for designated user Stephen Eaves. No other reproduction or transmission in any
`form permilted without written permission af NFPA. For inquiries of fo repart unauthorized use, contact licensing@nfoa.arg.
`
`ARTICLE 430 — MOTORS, MOTOR CIRCUITS, AND CONTROLLERS
`
`tional warning sign{s) shall be located where visible to persons who may
`be working in the avea of the energized parts.
`
`Exception No. 2: The motor control circuit disconnecting means shall be
`permitted to be remotefrom the motor controller power supply disconnect-
`ing means where the opening of one or more motor control circuit
`disconnecting means is capable of resulting in potentially unsafe condi-
`fionsfor personnel or property and the conditions of items (a) and (b) of
`Exception No. I are complied with,
`(B) Control Transformer in Controller Enclosure. Where a
`transformer or other device is used to obtain a reduced voltage
`for the motor control circuit and is located m the controller
`enclosure, such transformer or other device shall be connected
`to the load side of the disconnecting means for the motor
`control circuit.
`
`Part Vil. Motor Controllers
`
`Part VII
`430.81 General.
`controllers for all motors.
`
`is
`
`intended to require suitable
`
`(A) Stationary Motor of 4 Horsepower or Less. For a station-
`ary motor rated at % hp or less that is normally left running
`and is constructed so that it cannot be damaged by overload or
`failure to start, such as clock motors and the like, the branch-
`circuit disconnecting means shall be permitted to serve as the
`controller.
`
`(B) Portable Motor of '4 Horsepower or Less. For a portable
`motor rated at 4 hp orless, the controller shall be permitted to
`be an attachment plug and receptacle or cord connector.
`
`430.82 Controller Design.
`
`[ach controller shall be capable of
`(A) Starting and Stopping.
`starting and stopping the motorit controls and shall be capable
`of interrupting the locked-rotor current of the motor.
` shali
`(B) Autotransformer.
`An
`autotransformer
`starter
`provide an “off” position, a running position, and at least one
`starting position. It shall be designed so that it cannot rest in
`the starting position or in any position that will render the
`overload device in the circuit inoperative.
`
`(G) Rheosiats. Rheostats shall be in compliance with the
`following:
`(1) Motorstarting rheostats shall be designed so that the
`contact arm cannot be left on intermediate segments.
`The point or plate on which the arm rests when in the
`starting position shall have no electrical connection with
`the resistor.
`(2) Motorstarting rheostats for dc motors operated from a
`constant voltage supply shall be equipped with automatic
`devices that will interrupt the supply before the speed of
`the motor has fallen to less than one-third its normalrate.
`
`430.83 Ratings. The controller shall have a rating as specified
`in 430.83(A), unless otherwise permitted in 430.83(B) or (C),
`or as specified in (D), under the conditions specified.
`(A) General.
`
`(1) Horsepower Ratings. Controllers, other than inverse time
`circuit breakers and molded case switches, shall have horse-
`power ratings at the application voltage not lower than the
`horsepower rating of the motor.
`
`inverse time circuit
`(2) Circuit Breaker. A branch-circuit
`breaker rated in amperes shall be permitted as a controller for
`all motors. Where this circuit breaker is also used for overload
`protection, it shall conform to the appropriate provisions of
`this article governing overload protection.
`
`(3) Molded Case Switch. A molded case switch rated in
`amperesshall be permitted as a controller for all motors.
`
`(B) Small Motors. Devices as specified in 430.81{A) and (B)
`shall be permitted as a controller,
`
`(C) Stationary Motors of 2 Horsepower or Less. For station-
`ary motors rated at 2 hp or less and 300 volts or less,
`the
`controller shall be permitted to be either of the following:
`(1) A general-use switch having an ampere rating not less
`than twice the fullioad currentrating of the motor
`(2) On ac circuits, a generaluse snap switch suitable only for
`use on ac {not generaluse ac-de snap switches) where
`the motor full-load current rating is not more than
`80 percent of the ampererating of the switch
`
`(D) Torque Moters. For torque motors, the controller shall
`have a continuous-duty, fullload current rating not less than
`the nameplate current rating of the motor For a motor
`controller rated in horsepower but not marked with the forego-
`ing current rating, the equivalent current rating shall be deter-
`mined from the horsepower rating by using Table 430,247,
`Table 430.248, Table 430.249, or Table 430.250.
`
`(E) Voltage Rating. A controller with a straight voltage rating,
`for example, 240 volts or 480 volts, shall be permitted to be
`applied in a circuit in which the nominal voltage between any
`two conductors does not exceed the controller’s voltage rating.
`A controller with a slash rating, for example, 120/240 volts or
`480Y/277 volts, shall only be applied in a solidly grounded
`circuit
`in which the nominal voltage to ground from any
`conductor does not exceed the lower of the two values of the
`controller’s voltage rating and the nominal voltage between
`any two conductors does not exceed the higher value of the
`controller’s voltage rating.
`
`430.84 Need Net Open All Conductors. The controller shall
`not be required to open all conductors to the motor.
`
`Exception: Where the controller serves also as a disconnecting means, tt
`shall open ail ungrounded conductors to the motor as provided im
`430,111,
`
`430.85 In Grounded Conductors. One pole of the controller
`shall be permitted to be placed in a permanently grounded
`conductor, provided the controller is designed so that the pole
`in the grounded conductor cannot be opened without simuita-
`neously opening all conductors of the circuit.
`
`430.87 Number of Motors Served by Each Controller. Each
`motor shall be provided with an individual controller.
`
`Exception No. 1: For motors rated 10G0 volts orless, a single controller
`rated at not
`less than the equivalent hersepower, as determined in
`accordance with 430. 110{(C)(1), of all the motors in the group shall be
`permitted to serve the group under anyof thefollawing conditions:
`(a} Where a number of motors drive several parts of a single
`machine or prece of apparatus,
`such as metal and woodworking
`machines, cranes, hoists, and similar apparatus
`(6) Where a group of motors is under the protection of one over-
`current device as permitted in. 430,53(A)
`
`Page 315 of 881
`
`

`

`Copyright 2016 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and download on 10/18/2016 to VollServer for designated user Stephen Eaves. No other reproduction or transmission in any
`form permitted without written permission af NFPA, For inquities or to report unauthorized use, contactlicensing@infpa.org
`
`ARTICLE 480 — MOTORS, MOTOR CIRCUITS, AND CONTROLLERS
`
`450.99
`
`(c) Where a group of moiors is located in a single room within
`sightfrom the controller location
`
`connecting the grounded conductor, onits supply side, to the
`motor control center equipment ground bus,
`
`Exception No. 2: A branch-circuit disconnecting means serving as the
`controller as allowed in 436.81(A) shall he permitted to serve more than
`one motor
`
`Exception: High-impedance grounded neutral systems shall be permitted
`to be connected as provided in 250.36,
`
`430.88 AdjustableSpeed Motors. Adjustable-speed motors
`that are controlled by meansoffield regulation shall be equip-
`ped and connected so that they cannot be started under a
`weakened field.
`
`Exception: Starting under a weakened field shall be permitted where the
`motoris designedfor such starting.
`
`430.89 Speed Limitation. Machines of the following types
`shall be provided with speed-limiting devices or other speed-
`limiting means:
`:
`Separately excited dc motors
`Series motors
`(3) Motor-generators and converters that can be driven at
`excessive speed from the de end, as by a reversal of
`current or decrease in load
`
`Exception: Separate speed-limiting devices or means shail not be
`required undereither of thefollowing conditions:
`the system, or
`(1) Where the inherent characieristics of the machines,
`the load and the mechanical connection thereto are such as to
`safely limit the speed
`(2) Where the machine is always under the manual control of a
`qualified operator
`430.90 Combination Fuseholder and Switch as Controller.
`The rating of a combination fuseholder and switch used as a
`motor controller shall be such that the fusehoider will accom-
`modate the size of the fuse specified in Part II of this article
`for motor overload protection.
`
`Exception: Where fuses having time delay appropriate for the starting
`characteristics of the motor ave used, fusehoiders of smaller size than
`specified in Part IH ofthis article shall be permitted.
`
`Part Vill. Moter Control Centers
`
`450.92 General. Part VHI covers motor control centers instal-
`led for the control of motors, lighting, and powercircuits.
`430.94 Overcurrent Protection. Motor control centers shall
`be provided with overcurrent protection in accordance with
`Parts I, If, and VHI of Article 240, The ampere rating or setting
`of the overcurrent protective device shall not exceed the rating
`of the common powerbus. This protection shall be provided by
`(1) an overcurrent protective device located ahead of the
`motor control center or (2) a main overcurrent protective
`device located within the motor contro! center.
`
`430,95 Service Equipment. Where used as service equipment,
`each motor control center shall be provided with a single main
`disconnecting means to disconnect ali ungrounded service
`conductors.
`
`Exception: A second service disconnect shall be permitted to supply
`additional equipment.
`
`Wherea grounded conductor is provided, the motor control
`center shall be provided with a main bonding jumper,sized in
`accordance with 250.28(D), within one of the sections for
`
`430.96 Grounding. Multisection motor control centers shail
`be connected together with an equipment grounding conduc-
`tor or an equivalent equipment grounding bus sized in accord-
`ance with Table 250.122. Equipment grounding conductors
`shall be connected to this equipment grounding bus or to a
`grounding termination point provided im a single-section
`motor control center.
`
`450.97 Busbars and Conductors.
`
`(A) Support and Arrangement. Busbars shali be protected
`from physical damage and be held firmly in place. Other than
`for required interconnections and control wiring, only those
`conductors that are intended for termination in a vertical
`section shall be located in that section.
`
`Exception: Conductors shall be permitted to travel horizontally through
`vertical sections where such conductors are isolated from the busbars by
`a barrier.
`
`(B) Phase Arrangement. The phase arrangement on 3-phase
`horizontal common power and vertical buses shall be A, B, G
`from front to back, top to bottom, or left to right, as viewed
`from the front of the motor control center. The B phase shall
`be that phase having the higher voltage to ground on 3-phase,
`4wire, delta-connected systems. Other busbar arrangements
`shall be permitted for additions to existing installations and
`shall be marked.
`
`is
`Exception: Rearmounied units connected to a vertical bus that
`common to front-mounted units shall be permitted io have a C, B, A
`phase arrangement where properly identified.
`
`(C} Minimum Wire-Bending Space. The minimum wire-
`bending space at the motor control center terminals and mini-
`mum gutter space shall be as required in Article 312(D).
`
`Spacings between motor control center bus
`{D) Spacings.
`terminals and other bare metal parts shall not be less than
`specified in Table 430.97(D).
`
`(E) Barriers. Barriers shall be placed in all service-entrance
`motor control centers to isolate service busbars and terminals
`from the remainder of the motor control center.
`
`430.98 Marking.
`(A) Motor Control Centers. Motor control centers shall be
`marked according to 110.21, and the marking shall be plainly
`visible after installation. Marking shali also include common
`power bus current rating and motor control center short-
`cirenit rating.
`
`(B) Motor Contrel Units. Motor control units in a motor
`control center shali comply with 430.8.
`N 430.99 Available Fault Current. The available short circuit
`eurrent at the motor control center and the date the short
`circuit current calculation was performed shali be documented
`and made available to those authorized to inspect the installa-
`tion.
`
`Page 316 of 881
`
`

`

`Copyright 2016 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and downioad on 10/18/2016 to VoltGerver for designated user Stephen Eaves. No other reproduction of transmission in any
`form permitted without written permission of NFPA, For inquiries or io report unauthorized use, contact ficensing@nfpa.arg.
`
`ARTICLE 430 — MOTORS, MOTOR CIRCUITS, AND CONTROLLERS
`
`Table 430.97(D) Minimum Spacing Between Bare Metal Parts
`
`
`Opposite Polarity Where Held
`Opposite Polarity Where Mounted
`
`on the Same Surface
`Free in Air
`Live Parts to Ground
`
`Nominal Voltage
`mm
`in,
`mm
`in.
`mm
`in.
`Not over 125 volts, nominal
`19.1
`x,
`12.7
`%
`12.7
`y%
`Notover 250 volts, nominal
`31.8
`1%
`19.1
`A
`12.7
`ye
`Not over 600 volts, nominal
`50.8
`2
`25.4
`1
`25,4
`1
`
`Part IX. Disconnecting Means
`
`430.101 General. Part IX is intended to require disconnect-
`ing means capable of disconnecting motors and controllers
`from the circuit.
`
`Informational Note: Some examples of increased or additional
`hazards include, but are not limited to, motors rated in excess of
`100 hp, multimetor equipment, submersible motors, motors
`associated with adjustable speed drives, and motors located in
`hazardous (classified) locations.
`
`430.102 Location.
`
`(A) Controller. An individual disconnecting means shall be
`provided for each controller and shal! disconnect the control
`ler. The disconnecting means shall be located in sight from the
`controller location.
`
`Exception No. 1: For motorcircuits over 1000 valts, nominal, a control
`ler disconnecting means lockable in accordance with 110.25 shall be
`permitted to be out of sight of the controller, provided that the controller
`is marked with a warning label giving the location of the disconnecting
`
`Exception No. 2: A single disconnecting means shall be permitted for a
`group of coordinated controllers that drive several parts of a single
`machine or plece of apparatus. The disconnecting means shall be loca-
`ied in sight from the controllers, and both ihe disconnecting means and
`the controllers shall be located in sight from ihe machine or apparatus.
`
`Exception No. 3: The disconnecting means shall not be requared to be in
`sight from valve actuator motor (VAM) assemblies containing the
`controller where such a location introduces additional or increased
`hazards to persons or property and conditions (a) and (b} are met.
`The vatve actuator motor assembly is marked with a warn-
`ing label giving the location of the disconnecting means.
`The disconnecting means is lochable in accordance with
`
`In industrial installations, with written safety procedures,
`{b}
`where conditions of maintenance and supervision ensure that only
`qualified persons service ihe equipment
`Informational Note: For information on lockout/tagout proce-
`dures, see NFPA 70H-2015, Standardfor Electricat Safety in the Work-
`place.
`
`430,103 Operation. The disconnecting means shall open ali
`ungrounded supply conductors and shall be designed so that
`no pole can be operated independently. The disconnecting
`means shall be permitted in the same enclosure with the
`controiler, The disconnecting means shall be designed so that
`it cannot be closed automaticaily.
`Informational Note: See 430.113 for equipment
`energy from more than one source.
`
`receiving
`
`430.104 To Be Indicating. The disconnecting means shall
`plainly indicate whetherit is in the open (off) or closed (on)
`position.
`
`430.105 Grounded Conductors. One pole of the disconnect
`ing means shall be permitted to disconnect a permanently
`grounded conductor, provided the disconnecting means is
`designed so that the pole in the grounded conductor cannot
`be opened without simultaneously disconnecting all conduc-
`tors of the circuit.
`
`(B) Motor. A disconnecting means shall be provided for a
`motor in accordance with (B}(1) or (B){2).
`
`430.107 Readily Accessible. At least one of the disconnecting
`means shall be readily accessible.
`
`(1) Separate Motor Disconnect. A disconnecting means for
`the motorshall be located in sight from the motor location and
`the driven machinery location,
`
`The controller disconnecting
`(2) Contreller Disconnect.
`means required in accordance with 430.102(A) shall be permit-
`ted to serve as the disconnecting means for the motorif it is in
`sight from the motor location and the driven. machinery loca-
`
`Exception to (1) and (2): The disconnecting means for the motorshall
`not be required under either condition (a} or condition {b), which
`follow, provided that the controller disconnecting means required in
`430. 102A)is lockable in accordance with 110.25.
`{a} Where such a location of the disconnecting means for the
`motor is impracticable or introduces additional or increased hazards to
`persons or property
`
`Every disconnecting
`430.108 Every Disconnecting Means.
`means in the motor circuit between the point of attachment to
`the feeder or branch circuit and the point of connection to the
`moter shail comply with the requirements of 430.109 and
`430.1106.
`
`430.109 Type. The disconnecting means shall be a type speci-
`fied in 430.109(A), unless otherwise permitted in 430.109(B}
`through (G), under the conditions specified.
`
`(A) General.
`
`(1) Motor Circuit Switch.
`horsepower.
`(2} Molded Case Circuit Breaker. A listed moided case circuit
`breaker,
`
`<A listed motorcircuit switch rated in
`
`(3} Molded Case Switch. A listed molded case switch.
`
`Page 317 of 881
`
`

`

`Copyright 2016 National Fire Protection Association (NFPA), Licensed, by agreement,for individual use and download on 10/18/2076 to VoltServer for designated user Stephen Eaves. No other repraduction or transmission in any
`form permitted without written permission of NFPA. For inquiries or to report unauthorized use, contact licensing@alba org.
`
`ARTICLE 430 — MOTORS, MOTOR CIRCUITS, AND CONTROLLERS
`
`430.110
`
`(4) Instantaneous Trip Circuit Breaker. An instantaneous trip
`circuit breaker that is part of a listed combination motor
`controller.
`
`self
`
`Listed
`
`(5) Self&Protected Combination Controller.
`protected combination controller,
`(6) Manual Moter Controller. Listed manual motor control-
`lers additionally marked “Suitable as Motor Disconnect” shall
`be permitted as a disconnecting means where installed between
`the final motor branch-circuit short-circuit protective device
`and the motor. Listed manual motor controllers additionally
`marked“Suitable as Motor Disconnect” shall be permitted as
`disconnecting means on theline side of the fuses permitted in
`430.52(C) (5). In this case, the fuses permitted in 430.52(C) (5)
`shall be considered supplementary fuses, and suitable branch-
`circuit short-circuit and ground-fault protective devices shall be
`installed on the line side of the manual motor controller addi-
`tionally marked “Suitable as Motor Disconnect.”
`
`(7) System Isolation Equipment. System isolation equipment
`shall be listed for disconnection purposes. System isclation
`equipment shali be installed on the load side of the overcur-
`rent protection and its disconnecting means. The disconnect
`ing meansshall be one of the types permitted by 430.109(A) (1)
`through (A) {3}.
`
`(B) Stationary Motors of 4 Horsepower or Less. Forstation-
`ary motors of 4% hp or less,
`the branch-circuit overcurrent
`device shall be permitted to serve as the disconnecting means.
`
`(C) Stationary Motors of 2 Horsepower or Less. For station-
`ary motors rated at 2 hp or less and 300 volts or less, the discon-
`necting means shall be permitted to be one of the devices
`specified in (1), (2), or (3):
`(1) A general-use switch having an ampere rating not less
`than twice the fulldoad current rating of the motor
`(2) On ac circuits, a general-ause snap switch suitable only for
`use on ac (not generabuse ac-dc snap switches) where
`the motor full-load current rating is not more than
`80 percent of the ampererating of the switch
`(3} A fisted manual motor controller haying a horsepower
`rating not less than the rating of the motor and marked
`“Suitable as Motor Disconnect”
`
`(DB) Autotransformer-Type Controlled Motors. For motors of
`over 2 hp to and including 100 hp, the separate disconnecting
`means required for a motor with an autotransformertype
`controller shall be permitted to be a general-use switch where
`all of the following provisions are met:
`(1) The motor drives a generator that is provided with over-
`load protection.
`(2) The controller is capable of interrupting the locked-rotor
`current of the motors,
`is provided with a no voltage
`release, and is provided with running overload protection
`not exceeding 125 percent of the motor full-load current
`rating.
`Separate fuses or an inverse time circuit breaker rated or
`set at not more than 150 percent of the motor fullload
`current is provided in the motor branchcircuit.
`
`(E) Isolating Switches. For stationary motors rated at more
`than 40 hp de or 100 hp ac, the disconnecting means shall be
`permitted to be a general-use or isolating switch where plainly
`marked “Do not operate under load.”
`
`(F) Cord-and-Plug-Connected Motors. For a cord-and-plug-
`connected motor, a horsepowerrated attachment plug and
`receptacle, flanged surface inlet and cord connector, or attach-
`ment plug and cord connector having ratings no less than the
`motor ratings shall be permitted to serve as the disconnecting
`means. Horsepower-rated attachment plugs, flanged surface
`inlets, receptacies, or cord connectors shall not be required for
`cord-and-plug-connected appliances in accordance with 422.33,
`room air conditioners in accordance with 440.63, or portable
`motors rated 4 hp orless.
`
`the disconnecting
`(G) Torque Motors. For torque motors,
`means shall be permitted to be a general-use switch.
`
`430.110 Ampere Rating and Interrupting Capacity.
`
`(A} General. The disconnecting means for motor circuits
`rated 1060 volts, nominal, or jess shall have an ampere rating
`not less than 115 percent of the fulltoad current rating of the
`motor.
`
`Exception: A listed unfused motor-circuit switch having a horsepower
`rating not less than. the motor horsepower shall be permitted to have an
`ampere rating less than LL) percent of the full-load current rating of
`the motor.
`
`(B) For Torque Motors. Disconnecting means for a torque
`motor shall have an ampere rating of at least 115 percent of the
`motor nameplate current.
`(C) For Combination Loads. Where two or more motors are
`used together or where one or more motors are used in combi-
`nation with ether loads, such as resistance heaters, and where
`the combined load may be simultaneous on a single discon-
`necting means,
`the ampere and horsepower ratings of the
`combined load shall be determined as follows.
`
`(1) Horsepower Rating. The rating of the disconnecting
`means shall be determined from the sum of all currents,
`including resistance loads, at the full-load condition and also at
`the locked-rotor condition. The combined fullload current
`and the combined locked-rotor current so obtained shall be
`considered as a single motor for the purpose of this require-
`ment as follows.
`
`The full-ioad current equivalent to the horsepowerrating of
`each motor
`shall
`be
`selected
`from Tabie
`430,247,
`Table 430.248, Table 430.249, or Table 430.250. These fullioad
`currents shall be added to the rating in amperes of other loads
`to obtain an equivalent fullload current for the combined
`load.
`
`to the horsepower
`The locked-rotor current equivalent
`rating of each motor shall be selected from Table 430.251 (A)
`or Table 430.251(B). The locked-rotor currents shall be added
`to the rating in amperes of other loads to obtain an equivalent
`locked-rotor current for the combined load. Where two or
`more motors or other loads cannot be started simultaneously,
`the largest sum of locked-rotor currents of a motor or group of
`motors that can be started simultaneously and the fullioad
`currents of other concurrent loads shall be permitted to be
`used to determine the equivalent locked-rotor current for the
`simultaneous combined loads. In cases where different current
`
`Page 318 of 881
`
`

`

`Copyright 2016 National Fire Protection Association (NFPA), Licensed, by agreement, for individual use and download on 16/18/2016 to VoltServer for designated user Stephen Eaves. No other reproduction or transmission in any
`form permitted without written permission of NFPA, For inquiries of te repart unauthorized use, contact icensing@nfpa org.
`
`ARTICLE 430 — MOTORS, MOTOR CIRCUITS, AND CONTROLLERS
`
`ratings are obtained when applying these tables, the largest
`value obtained shall be used.
`
`Exception: Where part of the concurrent load is resistance load, and
`where the disconnecting means is a switch rated in horsepower and
`amperes, the switch used shall be permitted to have a horsepowerrating
`that is not less than the combined load of the motor(s), if the ampere
`rating of the switch is nat
`less than the locked-roter current of the
`motar(s) plus the resistance load.
`
`(2) Ampere Rating. The ampere rating of the disconnecting
`means shall not be less than 115 percent of the sum of all
`currents at the fullload condition determined in accordance
`with 430.110(C) (1).
`
`Exception: A listed nonfused motor-circuit switch having a horsepower
`rating equal
`to or greater than the equivalent horsepower of the
`combined loads, determined in accordance with 430. 110(C)(1), shalt
`be permitied to have an ampere rating less than 115 percent of the sum
`ofall currenis at thefull-load condition.
`
`(3) Small Moters. For small motors not covered by Table
`430.247, Table 430.248, Table 450.249, or Table 430.250, the
`locked-rotor current shail be assumed to be six times the full-
`load current.
`
`430.111 Switch or Circuit Breaker as Both Controller and
`Disconnecting Means.
`<A switch or circuit breaker shall be
`permitted to be used as both the controller and disconnecting
`means if it complies with 430.111(A) and is ome of the types
`specified in 430.111(B).
`
`(A) General. The switch or circnit breaker complies with the
`requirements for controllers specified in 430.83, opens all
`ungrounded conductors to the motor, and is protected by an
`overcurrent device in each ungrounded conductor (which shall
`be permitted to be the branch-circuit fuses}, The overcurrent
`device protecting the controller shall be permitted to be part of
`the controller assembly or shall be permitted to be separate. An
`aultotransformer-type controller shall be provided with a sepa-
`rate disconnecting means.
`
`(B) Type. The device shall be one of the types specified in
`430.111(B)(1), (B) (2), or (B) (3).
`
`{a} Where a number of motors drive several paris of a single
`machine or plece of apparatus, such as metal and wood

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket