throbber
60950-1 © |EC:2005+A1:2009
`+A2i20‘l3
`
`— 123 —
`
`2.10.12 Enclosed and sealed parts
`
`For components or subassemblies that are adequately enclosed by enveloping or hermetic
`seating to prevent ingress of dirt and moisture. the values for Pollution Degree 1 apply to
`internal CLEARANCES and CREEPAGE DISTANCES.
`
`NOTE Some examples of such construction include parts in boxes that are hermetically sealed by adhesive or
`otherwise. and parts enveloped in a dip coat.
`
`if necessary, by
`Compliance is checked by inspection from the outside, measurement and,
`test. A component or subassembly is considered to be adequately enclosed if a sample
`passes the tests of 2.10.10.
`
`3 Wiring, connections and supply
`
`3.1 General
`
`3.1.1 Current rating and overcurrent protection
`
`The cross-sectional area of internal wires and lNTERCONNECTlNG CABLES shall be adequate for
`the current they are intended to carry when the equipment is operating under NORMAL LOAD
`such that the maximum permitted temperature of conductor insulation is not exceeded.
`
`All internal wiring (including busbars) and INTERCONNECTING CABLES used in the distribution of
`PRIMARY ciacun power shall be protected against cvercurrent and short—circuit by suitably
`rated protective devices.
`
`Wiring not directly involved in the distribution path does not require protection it
`shown that creation of hazards is unlikely (for example, indicating circuits).
`
`it can be
`
`NOTE 1 Devices for overload protection of components may also provide protection ofassociated wiring.
`NOTE 2
`Internal circuits connected to a MAINS SUPPLY may require individual protection depending on reduced
`wire size and length of conductors.
`
`Compliance is checked by inspection and, as appropriate, by the tests of 4.5.2 and 4.53.
`
`3.1.2 Protection against mechanical damage
`
`Wireways shall be smooth and free from sharp edges. Wires shall be protected so that they
`do not come into contact with burrs, cooling fins, moving parts, etc.. which could cause
`damage to the insulation of conductors. Holes in metal, through which insulated wires pass.
`shall have smooth well-rounded surfaces or shall be provided with bushings.
`
`It is permitted for wires to be in close contact with wire wrapping posts and the like if any
`breakdown of insulation will not create a hazard, or if adequate mechanical protection is
`provided by the insulation system.
`
`Compliance is checked by inspection.
`
`3.1.3 Securing of internal wiring
`
`internal wiring shall be routed, supported, clamped or secured in a manner that reduces the
`likelihood of:
`
`—
`
`—
`
`_
`
`excessive strain on wire and on terminal connections; and
`
`loosening of terminal connections; and
`
`damage of conductor insulation.
`
`Page 125 of 648
`
`VOLTSERVER EXHIBIT 1023 (part 3 of 11)
`
`

`

`— 124 —
`
`50950—1©|EC:2005+A1:2009
`+A2:2013
`
`3.1.4
`
`Insulation of conductors
`
`Except as covered in 2.1.1.3 b), insulation of individual conductors of internal wiring shall fulfil
`the requirements of 2.10.5 and be capable of withstanding the applicable electric strength test
`specified in 5.2.2.
`
`Where a power supply cord, whose insulating properties comply with those of the cord types
`0f3.2,5,
`is used inside the equipment. either as an extension of the external power supply
`cord or as an independent cable, the sheath of the power supply cord is considered to be
`adequate SUPPLEMENTARY INSULATION for the purpose of 3.1.4.
`
`NOTE Requirements regarding colours of insulation are in 2.5.3.5.
`
`Compliance is checked by inspection and evaluation of test data showing that the insulation
`withstands the relevant test voltage.
`
`If such applicable test data is not available, compliance is checked by applying the electric
`strength test using a sample of approximately 1 m in length and by applying the relevant test
`voltage as follows:
`
`— for insulation of a conductor: by the voltage test method given in Clause 3 of ”EC 60885—1,
`using the relevant test voltage in 5.2.2 in this standard for the grade of insulation under
`consideration; and
`
`— for SUPPLEMENTARY lNSULATlON (for example, sleeving around a group of conductors):
`between a conductor inserted into the sleeve and metal foil wrapped tightly round the
`sleeve for a length ofat least 100 mm.
`
`3.1.5 Beads and ceramic insulators
`
`Beads and similar ceramic insulators on conductors shall:
`
`,
`
`—
`
`be so fixed or supported that they cannot change their pesition in such a way that a
`hazard would be created; and
`
`not rest on sharp edges or sharp corners.
`
`if beads are located inside flexible metal conduits, they shall be contained within an insulating
`sleeve, unless the conduit is mounted or secured in such a way that movement in normal use
`would not create a hazard.
`
`Compliance is checked by inspection and, where necessary, by the following test.
`
`A force of 10 N is applied to the insulators or to the conduit. The resulting movement, it any,
`shall not create a hazard in the meaning of this standard.
`
`3.1.6 Screws for electrical contact pressure
`
`Where electrical contact pressure is required. a screw shall engage at least two complete
`threads into a metal plate, a metal nut or a metal insert.
`
`including
`insulating material shall not be used where electrical connections,
`Screws of
`protective earthing, are involved, or where their replacement by metal screws could impair
`SUPPLEMENTARY INSULATlON or REINFORCED INSULATION.
`
`Where screws of insulating material contribute to other safety aspects, they shall be engaged
`by at least two complete threads.
`
`NOTE See also 2.5.5.? for screws used for protective earthing continuity.
`
`Page 126 of 648
`
`

`

`60950—1 © lEC:2005+A1:2009
`+A2:2013
`
`— 125 —
`
`3.1.7
`
`insulating materials in electrical connections
`
`Electrical connections, including those for protective earthing functions (see 2.6), shall be so
`designed that contact pressure is not transmitted through insulating material unless there is
`sufficient
`resilience in the metallic parts to compensate for any possible shrinkage or
`distortion of the insulating material.
`
`Compliance is checked by inspection.
`
`3.1.8 Self-tapping and spaced thread screws
`
`Spaced thread (sheet metal) screWs shall not be used for the connection of current—carrying
`parts, unless they clamp these parts directly in contact with each other and are provided with
`a suitable means of locking.
`
`Self-tapping (thread-cutting or thread-forming) screws shall not be used for the electrical
`connection of current-carrying parts, unless they generate a full form standard machine screw
`thread. Moreover, such screws shall not be used if they are operated by the USER or installer
`unless the thread is formed by a swaging action.
`
`NOTE See also 2.6.5.? for screws used for protective eartbing continuity.
`
`Compliance is checked by inspection.
`
`3.1.9 Termination of conductors
`
`fixing), or be so
`Conductors shall be provided with a means (for example, barriers or
`terminated, that they and their terminators (for example. ring terminals and flat quick-connect
`terminals) cannot,
`in normal use, become so displaced that CLEARANCES or CREEPAGE
`DISTANCES are reduced below the values specified in 2.10 (or Annex (3).
`
`it is permitted to use soldered, welded, crimped, screwiess (push~in) and similar terminations
`for the connection of conductors. For soldered terminations, the conductor shall be positioned
`or fixed so that reliance is not placed upon the soldering alone to maintain the conductor in
`position,
`
`In multiway plugs and sockets, and wherever shorting could otherwise occur. means shall be
`provided to prevent contact between parts in SELV CIRCUITS or TNV ClRCUlTS and parts at
`HAZARDOUS VOLTAGE due to loosening of a terminal or breaking of a wire at a termination.
`
`Compliance is checked by inspection, by measurement and, where necessary, by the
`following last.
`
`A force of 10 N is applied to the conductor near its termination point. The conductor shall not
`break away or pivot on its terminal to the extent that CLEARANCES or CREEPAGE DISTANCES are
`reduced below the values specified in 2.10 (or Annex G).
`
`For the purpose of assessing compliance it is assumed that:
`
`— two independent fixings will not become loose at the same time; and
`
`— parts fixed by means of screws or nuts provided with self—locking washers or other means
`of locking are not liable to become loose.
`
`NOTE Spring washers and the like can provide satisfactory locking.
`
`Examples of constructions regarded as meeting the requirements include:
`
`a close-fitting tubing (for example, a heat shrink or rubber sleeve), applied over the wire and
`
`Page 127 of 648
`
`

`

`— 126 —
`
`60950-1 © |EC:2005+A1:2009
`+A2.'2013
`
`— conductors connected by soldering and held in place near
`independently of the soldered connection;
`
`to
`
`the
`
`termination,
`
`w conductors connected by soldering and "hooked in " before soldering, provided that the
`hole through which the conductor is passed is not unduly large;
`
`— conductors connected to screw terminals, with an additional fixing near to the terminal that
`clamps, in the case of stranded conductors, the insulation and not only the conductors;
`
`— conductors connected to screw terminals and provided with terminators that are unlikely to
`become free (for example, ring lugs crimped onto the conductors). The pivoting of such
`terminators is considered;
`
`— short rigid conductors that remain in position when the terminal screw is loosened.
`
`3.1.10
`
`Sleeving on wiring
`
`Where sleeving is used as SUPPLEMENTARY INSULATION on internal wiring.
`in position by positive means.
`
`it shall be retained
`
`Compliance is checked by inspection.
`
`Examples of constructions that are considered to meet the intent of this requirement include:
`
`— sleeving that can be removed only by breaking or cutting of either the wiring or sleeving;
`
`fl
`
`sleeving that is clamped at both ends;
`
`— heat shrinkable sleeving that tightens against the wire insulation;
`
`— sleeving that is of such length that it will not slip.
`
`3.2 Connection to a mains supply
`
`3.2.1 Means of connection
`
`3.2.1.1
`
`Connection to an a.c. mains supply
`
`For safe and reliable connection to an AC MAINS SUPPLY, equipment shall be provided with one
`of the following:
`
`e
`
`terminals for permanent connection to the supply;
`
`7
`
`a NON-DETACHABLE POWER SUPPLY CORD for permanent connection to the supply. or for
`connection to the supply by means of a plug;
`NOTE In many countries. it is a legal requirement to provide a plug that complies with the national wiring rules.
`
`—
`
`—
`
`an appliance inlet for connection of a DETACHABLE POWER SUPPLY CORD:
`
`a mains plug that is part of DIRECT PLUG—EN EQUIPMENT.
`
`Compliance is checked by inspection.
`
`3.2.1.2 Connection to a d.c. mains supply
`
`For safe and reliable connection to a Dc MAINS SUPPLY, equipment shall be provided with one
`of the following:
`
`—
`
`7
`
`—
`
`terminals for permanent connection to the supply;
`
`a NON—DETACHABLE POWER SUPPLY CORD for permanent connection to the supply, or for
`connection to the supply by means of a plug;
`
`an appliance inlet for connection of a DETACHABLE POWER SUPPLY CORD.
`
`Page 128 of 648
`
`

`

`60950—1 © |EC:2005+A1:2009
`+A2:2013
`
`~127 —
`
`Plugs and appliance inlets shall not be of a type that is used for AC MAINS SUPPLIES if a hazard
`could be created by their use. Plugs and appliance inlets shall be so designed that reverse
`polarity connections are prevented if a hazard could be created by such connection.
`
`is permitted for one pole of the DC MAENS SUPPLY to be connected both to an equipment
`It
`mains input terminal and to the main protective earthing terminal of the equipment.
`if any,
`provided the equipment installation instructions detail the proper earthing for the system.
`
`Compliance is checked by inspection.
`
`3.2.2 Multiple supply connections
`
`if equipment is provided with more than one supply connection (for example, with different
`voltages or frequencies or as backup power), the design shall be such that all of the following
`conditions are met:
`
`,
`
`,
`
`—
`
`separate means of connection are provided for different circuits: and
`
`supply plug connections.
`incorrect plugging; and
`
`if any, are not interchangeable if a hazard could be created by
`
`bare parts of an ELV CIRCUIT or parts at HAZARDOUS VOLTAGES, such as plug contacts, are
`not accessible to an OPERATOR when one or more connectors are disconnected.
`
`Compliance is checked by inspection and for accessibility, where necessary, by a test with the
`test finger, Figure 2A (see 2.1.1.1).
`
`3.2.3 Permanently connected equipment
`
`PERMANENTLY CONNECTED EQUIPMENT shall be provided with either:
`
`—
`—
`
`a set of terminals as specified in 3.3; or
`a NON-DETACHABLE POWER SUPPLY CORD.
`
`PERMANENTLY CONNECTED EQUIPMENT having a set of terminals shall:
`
`—
`
`—
`
`permit the connection of the supply wires after the equipment has been fixed to its
`suppon;and
`
`be provided with cable entries, conduit entries, knock—outs or glands, which allow
`connection of the appropriate types of cables or conduits.
`
`the cable entries shall be
`For equipment having a RATED CURRENT not exceeding 16A,
`suitable for cables and conduits having an overall diameter as shown in Table 3A.
`
`Conduit and cable entries and knock-outs for supply connections shall be so designed or
`located that the introduction of the conduit and cable does not affect the protection against
`electric shock. or reduce CLEARANCES and CREEPAGE DISTANCES below the vaiues specified
`in 2.10 (or Annex G).
`
`Compliance is checked by inspection, by a practical installation test and by measurement.
`
`Page 129 of 648
`
`

`

`— 128 —
`
`609504 © lEC:2005+A1:2009
`+A2i20’13
`
`Table 3A — Sizes of cables and conduits for equipment having
`a rated current not exceeding 16 A
`
`Number of conductors,
`including the
`PROTECTIVE EARTHING CONDUCTOR
`where provided
`
`Overall diameter
`mm
`
`conduits.
`
`15,0 (22,2)
`15.0 (22,2)
`20,0 (27,5)
`20,0 (27‘s)
`NOTE In Canada and the United States the dimensions in parentheses are the size of
`conduit opening required for terminating nominal 112 inch and 3M inch trade size
`
`3.2.4 Appliance inlets
`
`Appliance inlets shall meet all of the following:
`
`—
`
`—
`
`2
`
`be so located or enclosed that parts at HAZARDOUS VOLTAGE are not accessible during
`insertion or removal of the connector (appliance inlets complying with lEC 50309 or with
`lEC 60320 are considered to comply with this requirement); and
`
`be so located that the connector can be inserted without difficulty; and
`
`be so located that, after insertion of the connector, the equipment is not supported by the
`connector for any position of normal use on a flat surface.
`
`for accessibility, by means of the test finger,
`
`Compliance is checked by inspection and,
`Figure 2A (see 2.1.1.1).
`
`NOTE For Switzerland, see 3.2.1.1 Note.
`
`3.2.5 Power supply cords
`
`3.2.5.1 AC power supply cords
`
`.-
`
`-
`
`..ee
`
`.= e
`
`2
`
`.e--:.
`
`:-
`
`=
`
`-: --
`
`-
`
`-
`
`AMAINS SUPPLY cord shall be
`
`
`
`of the sheathed type and comply with the following as appropriate:
`
`-
`
`,
`
`if rubber insulated- sheathed, be of synthetic rubber and not lighter than ordinary tough
`rubber—sheathed flexible cord according to IEC 60245-1 (designation 50245 lEC 53);
`if PVC insulated sheathed:
`
`-
`
`-
`
`for equipment provided with a NON-DETACHABLE POWER SUPPLY CORD and having a
`mass not exceeding 3kg, be not
`lighter
`than light PVC sheathed flexible cord
`according to lEC 60227-12007 (designation 60227 lEC 52);
`
`for equipment provided with a NON-DETACHABLE POWER SUPPLY CORD and having a
`mass exceeding 3kg, be not
`tighter
`than ordinary PVC sheathed flexible cord
`according to lEC 60227—12007 (designation 60227 lEC 53);
`
`NOTE 1 There is no limit on the mass of the equipment if the equipment is intended for use with a DETACHABLE
`POWER SUPPLY cone.
`
`I
`
`-
`
`for equipment provided with a detachable power supply cord, be not lighter than light
`PVC sheathed flexible cord according to [EC 60227-12007 (designation 60227 lEC
`52);
`
`
`
`Page 130 of 648
`
`

`

`60950-1 © IEC:2005+A1:2009
`+A2:2013
`
`— 129 —
`
`
`
`-
`
`cords
`screened
`for
`IEC 60227-221997;
`
`of moveable
`
`equipment.
`
`the
`
`flexing
`
`test
`
`of
`
`3.1
`
`of
`
`NOTE 2 Although screened cords are not covered in the scope of IEC 60227-2,
`IEC 60227-2 are used.
`
`the relevant flexing tests of
`
`—
`
`other types of cords may be used if they have similar or better eiectro-mechanical and fire
`safety properties as above.
`
`NOTES Where national or regional standards exist.
`paragraph
`
`they can be used to show compliance with the above
`
`For equipment required to have protective earthing. a PROTECTIVE EARTHING CONDUCTOR shall
`be included in the MAINS SUPPLY cord.
`
`A MAINS SUPPLY cord shall have conductors with a cross-sectional area not less than those
`
`specified in Table SB.
`
`Compliance is checked by inspection. For screened cords, damage to the screen is
`acceptable provided that:
`
`—
`
`—
`
`during the flexing test the screen does not make contact with any conductor, and
`
`after the flexing test, the sample withstands the appropriate electric strength test between
`the screen and all other conductors.
`
`Page 131 of 648
`
`

`

`— 130 —
`
`60950—1 © |EC:2005+A1:2009
`+A222013
`
`Over
`Over
`
`Table 3B — Sizes of conductors
` Minimum conductor sizes
`
`
`
`
`AWG or kcmil
`
`Nominal
`RATED CURRENT of equipment
`
`
`
`[cross-sectional area
`A
`cross—sectional area
`
`in mmz]
`
`
`see Note 2
`mm2
`
`
`
` Up to and including 6
`
`6 up to and including
`‘10
` (0,75) b
`
`13
`10 up to and including
`(1.0) °
`
`
`(1.0) “
`13 up to and including
`16
`Over
`
`
`
` Over 15 up to and including 25
`
`
`
`
`
` Over 25 up to and including 32
`
`
` Over 32 up to and including 40
`
` Over 40 up to and including 63
`
`
` Over 63 up to and including 80
`
` Over 80 up to and including 100
` Over 100 up to and including 125
` Over 125 up to and including 150
`Over 160 up to and including 190
`
`Over 190 up to and including 230
`
`
`
` 250 kcmii [125]
`Over 230 up to and including 260
`
`300 kcmii
`[1521
`Over 250 up to and including 300
`
`
`Over 300 up to and including 340
`
`Over 340 up to and including 400
`Over 400 up to and including 460
`
`400 kcmil
`500 kcmil
`
`600 kcrnil
`
`[202]
`[253]
`
`[3041
`
`
`
`
`
`NOTE 1
`IEC 60320 specifies acceptable combinations of appliance couplers and flexible cords. including
`
`
`
`those covered by Footnotes a, b and c above. However, several countries have indicated that they do not
`
`accept all of the values listed in Table SB, particularly those covered by Footnotes a, b and c above.
`NOTE 2 AWG and kcmil sizes are provided for information only. The associated cross-sectional areas. in
`square brackets have been rounded to show significant figures only. AWG refers to the American Wire
`
`Gage and the term "cmil" refers to circular mils where 1 cmil
`is the area of a circle having a diameter of
`1 mil
`(one thousandth of an inch). These terms are commonly used to designate wire sizes in North
`
`America.
`
`
`a For RATED CURRENT up to 3 A. a nominal cross-sectional area of 0,5 mm2 is permitted in some countries
`
`
`
`provided that the length of the cord does not exceed 2 rn.
`
`
`not exceed 2 m.
`
`
`
`
`b The value in parentheses applies to DETACHABLE POWER SUPPLY cones fitted with the connectors rated 10 A
`in accordance with lEC 60320 (types 013. C115, 015A and {317) provided that the length of the cord does
`
`The value in parentheses applies to DETACHABLE POWER SUPPLY cones fitted with the connectors rated 16 A
`
`in accordance with IEC 60320 (types (319‘ C21 and C23) provided that the length of the cord does not
`
`exceed 2 rn.
`
`
`3.2.5.2 DC power supply cords
`
`A power supply cord for connection to the DC MAINS SUPPLY shall be suitable for the voltage,
`current and the physical abuses it is likely to encounter.
`
`Compliance is checked by inspection.
`
`3.2.6 Cord anchorages and strain relief
`
`For equipment with a NON—DETACHABLE POWER SUPPLY CORD, a cord anchorage shall be
`
`Page 132 of 648
`
`

`

`60950-1 ©1EC:2005+A1:2009
`+A222013
`
`— 131 —
`
`—
`
`—
`
`the connecting points ofthe cord conductors are relieved from strain. and
`
`the outer covering of the cord is protected from abrasion.
`
`It shall not be possible to push the cord back into the equipment to such an extent that the
`cord or its conductors, or both, could be damaged or internal parts of the equipment could be
`displaced.
`
`For NON-DETACHABLE POWER SUPPLY CORDs containing a PROTECTIVE EARTHING CONDUCTOR, the
`construction shall be such that if the cord should slip in its anchorage, placing a strain on
`conductors, the PROTECTIVE EARTHING CONDUCTOR will be the last to take the strain.
`
`The cord anchorage shall either be made of insulating material or have a lining of insulating
`material complying with the requirements for SUPPLEMENTARY INSULATION. However, where the
`cord anchorage is a bushing that
`includes the electrical connection to the screen of a
`screened power cord,
`this
`requirement shall not apply. The construction of
`the cord
`anchorage shall be such that:
`
`—
`
`—
`
`cord replacement does not impair the safety of the equipment: and
`
`for ordinary replacement cords. it is clear how relief from strain is to be obtained: and
`
`— the cord is not clamped by a screw that bears directly on the cord, unless the cord
`anchorage,
`including the screw,
`is made of
`insulating material and the screw is of
`comparable size to the diameter of the cord being clamped; and
`
`— methods such as tying the cord into a knot or tying the cord with string are not used; and
`
`—
`
`the cord cannot rotate in relation to the BODY of the equipment to such an extent that
`mechanical strain is imposed on the electrical connections.
`
`Compliance is checked by inspection and by applying the following tests that are made with
`the type of power supply cord supplied with the equipment.
`
`The cord is subjected to a steady pull of the value shown in Tabie'3C, applied in the most
`unfavourable direction. The test is conducted 25 times, each time for a duration of? s.
`
`the power supply cord shall not be damaged. This is checked by visual
`During the tests,
`inspection, and by an electric strength test between the power cord conductors and
`accessible conductive parts, at the test voltage appropriate for REINFORCED lNSULATiON.
`
`the power supply cord shall not have been longitudinally displaced by more
`After the tests,
`than 2 mm nor shall there be appreciable strain at the connections, and CLEARANCES and
`CREEPAGE DISTANCES shall not be reduced below the values specified in 2.10 (or Annex G).
`
`Table SC — Physical tests on power supply cords
`
`
`Mass (M) of the equipment
`kg
`
`
`Up to and including 1
`
`60
`Overt up to and including 4
`
`
`Over 4
`100
`
`
`
`
`3.2.7 Protection against mechanical damage
`
`Power supply cords shall not be exposed to sharp points or cutting edges within or on the
`surface of the equipment, or at the inlet opening or inlet bushing.
`
`Page 133 of 648
`
`

`

`w 132 _
`
`60950-1 © IECIZOOS+A1ZZOOQ
`+A2:2013
`
`The overall sheath of a NON-DETACHABLE POWER SUPPLY CORD shall continue into the
`equipment through any inlet bushing or cord guard and shall extend by at least half the cord
`diameter beyond the clamp ofthe cord anchorage.
`
`Inlet bushings. where used, shall
`
`—
`—
`
`be reliably fixed, and
`not be removable without the use of a TOOL.
`
`A metallic inlet bushing shall not be used in a non-metallic ENCLOSURE.
`
`An inlet bushing or cord guard secured to a conductive part that is not protectively earthed
`shall meet the requirements for SUPPLEMENTARY INSULATION.
`
`Compliance is checked by inspection and measurement.
`
`3.2.8 Cord guards
`
`A cord guard shall be provided at the power supply cord inlet opening of equipment that has a
`NDN-DETACHABLE POWER SUPPLY CORD, and which is HAND-HELD EQUIPMENT or iS intended to be
`moved while in operation. Alternatively, the inlet or bushing shall be provided with a smoothly
`rounded bell-mouthed opening having a radius of curvature equal to at least 150 % of the
`overall diameter of the cord with the largest cross-sectional area to be connected.
`
`Cord guards shall
`
`a
`
`—
`
`—
`
`—
`
`be so designed as to protect the cord against excessive bending where it enters the
`equipment,
`
`be of insulating material,
`
`be fixed in a reliable manner, and
`
`project outside the equipment beyond the inlet opening for a distance of at least five times
`the overall diameter or, for flat cords, at least five times the major overall cross-sectional
`dimension of the cord.
`
`Compliance is checked by inspection, by measurement and, where necessary, by the
`following test with the cord as deliVered with the equipment.
`
`The equipment is so placed that the axis of the cord guard, where the cord leaves it, projects
`at an angle of 45° when the cord is free from stress. A mass equal to 10 xng is then
`attached to the free end of the cord, where D is the overall diameter of, or for flat cords, the
`minor overall dimension of the cord, in millimetres,
`
`If the cord guard is of temperature-sensitive material, the testis made at 23 "C i 2 “C.
`
`Flat cords are bent in the plane ofleast resistance.
`
`immediately after the mass has been attached,
`nowhere be less than 1,5 D.
`
`the radius of curvature of the cord shall
`
`3.2.9 Supply wiring space
`
`The supply wiring space provided inside, or as part of, the equipment for permanent connection or
`for connection of an ordinary NON~DETACHABLE POWER SUPPLY CORD shall be designed:
`
`a
`
`to allow the conductors to be introduced and connected easily; and
`
`Page 134 of 648
`
`

`

`60950-1 ©|EC22005+A1i2009
`+A2:2013
`
`— 133 —
`
`—
`
`so that the uninsulated end of a conductor is unlikely to become free from its terminal, or,
`should it do so, cannot come into contact with:
`
`-
`
`a
`
`an accessible conductive part that is not protectively earthed; or
`
`an accessible conductive part of HAND—HELD EQUIPMENT; and
`
`e
`
`—
`
`—
`
`to permit checking before fitting the cover,
`connected and positioned; and
`
`if any,
`
`that
`
`the conductors are correctly
`
`if any, can be fitted without risk of damage to the supply conductors or
`so that covers,
`their insulation; and
`
`so that covers,
`available TOOL.
`
`if any, giving access to the terminals can be removed with a commonly
`
`Compliance is checked by inspection and by an installation test with cords of the largest
`cross—sectional area of the appropriate range specified in 3.3.4.
`
`3.3 Wiring terminals for connection of external conductors
`
`3.3.1 Wiring terminals
`
`PERMANENTLY CONNECTED EQUIPMENT and equipment with ordinary NON—DETACHABLE POWER
`SUPPLY CORDS shall be provided with terminals in which connection is made by means of
`screws, nuts or equally effective devices (see also 2.6.4).
`
`Compliance is checked by inspection.
`
`3.3.2 Connection of non-detachable power supply cords
`
`the connection of the
`For equipment with special NON~DETACHABLE POWER SUPPLY coacs,
`individual conductors to the internal wiring of the equipment shall be accomplished by any
`means that will provide a reliable electrical and mechanical connection without exceeding
`the permitted temperature limits while the equipment
`is operated under NORMAL LOAD
`(see also 3.1.9).
`
`Compliance is checked by inspection and by measuring the temperature of the connection
`which shall not exceed the values of 4.5.3, Table 45.
`
`3.3.3 Screw terminals
`
`Screws and nuts that clamp external MAth SUPPLY conductors shall have a thread conforming
`to lSO 261 or ISO 262, or a thread comparable in pitch and mechanical strength (for example,
`unified threads). The screws and nuts shall not serve to fix any other component, except that
`they are permitted also to clamp internal conductors provided that the internal conductors are
`so arranged that they are unlikely to be displaced when fitting the supply conductors. For
`protective earthing terminals and protective bonding terminals, see also 2.6.4.2.
`
`The terminals of a component (for example, a switch) built into the equipment are permitted
`for use as terminals for external MAINS SUPPLY conductors, provided that they comply with the
`requirements of 3.3.
`
`Compliance is checked by inspection.
`
`3.3.4 Conductor sizes to be connected
`
`Terminals shall allow the connection of conductors having nominal cross-sectional areas as
`shown in Table 3D.
`
`Page 135 of 648
`
`

`

`— 134 —
`
`609504 © |EC:2005+A1:2009
`+A2:2013
`
`Compliance is checked by inspection, by measurement and by fitting cords of the smallest
`and largest cross-sectional areas of the appropriate range shown in Table 30.
`
`Table SD — Range of conductor sizes to be accepted by terminals
`
`Nominal cross-sectional area
`
`RATED CURRENT of equipment
`A
`
`mm2
`Flexible cords
`Other cables
`
`Over 32 up to and including 40 Over 40 up to and Including 63
`
`3
`Up to and including
`3 up to and including 6
`
`Over
`
`6 up to and including 10
`Over
`Over 10 up to and including 13
`Over 13 up to and including 16
`Over 15 up to and including 25
`Over 25 up to and including 32
`
`3.3.5 Wiring terminal sizes
`
`Pillar, stud or screw type terminals shall comply with the minimum sizes in Table 3E.
`
`Compliance is checked by inspection and measurement.
`
`Table 3E — Sizes of terminals for mains supply conductors
`and protective earthing conductors a
`
`
`
`
`
`Page 136 of 648
`
`

`

`60950—1 © |EC:2005+A1:2009
`+A2i2013
`
`— 135 —
`
`RATED CURRENT
`A
`.
`.
`"P to and "‘6'“de
`
`Conductor size
`2
`mm
`
`Minimum nominal thread
`'
`diameter
`mm
`
`Pillar type or
`stud type
`3.0
`
`Screw type
`
`b
`
`3.5
`
`Area of cross section
`2
`
`mm
`
`Pillar type or
`stud type
`7
`
`Screw type "
`
`9,6
`
`IEC 60999-2.
`
`
`
`'
`
`“
`
`This table is also used for the sizes of terminals for PROTECTIVE BONDING CONDUCTORS if specified in
`2.6.4.2.
`
`"Screw type" refers to a terminal that clamps the conductor under the head of a screw. with or without a
`washer
`
`° As an alternative to the requirements of this table, the protective earthing conductor may be attached to
`special connectors. or suitable clamping means (for example. an upturned spade or closed loop pressure
`type; clamping unit type; saddle clamping unlt type; mantle clamping unit type; etc.) that is secured by a
`screw and nut mechanism to the metal chassis of the equipment, The sum of the cross-sectional areas of
`the screw and the nut shall not be less than three times the cross-sectional area of the conductor size in
`Table 20 or Table SB as applicable. The terminals shall comply with lEC 609954 and IEC 60999—1 or
`
`3.3.6 Wiring terminal design
`
`Wiring terminals shall be so designed that they clamp the conductor between metal surfaces
`with sufficient contact pressure and without damage to the conductor.
`
`Terminals shall be so designed or located that
`clamping screws or nuts are tightened.
`
`the conductor cannot slip out when the
`
`Terminals shall be provided with appropriate fixing hardware for the conductors (for example,
`nuts and washers).
`
`Terminals shall be so fixed that, when the means of clamping the conductor is tightened or
`loosened. all of the following apply:
`
`—
`
`—
`
`—
`
`the terminal itself does not work loose;
`
`internal wiring is not subjected to stress; and
`
`CLEARANCES and CREEPAGE DISTANCES are not reduced below the values specified in 2.10
`(or Annex G).
`
`Compliance is checked by inspection and measurement.
`
`3.3.7 Grouping of wiring terminals
`
`PERMANENTLY CONNECTED
`For ordinary NON-DETACHABLE POWER SUPPLY CORDS and for
`EQUIPMENT, all associated AC MAINS SUPPLY terminals shall be located in proximity to each
`other and to the main protective earthing terminal, if any.
`
`PERMANENTLY CONNECTED
`For ordinary NONrDETACHABLE POWER SUPPLY CORDS and for
`EQUIPMENT. all associated DC MAINS SUPPLY terminals shall be located in proximity to each
`other. They need not be located in proximity to the main protective earthing terminal,
`if any.
`
`Page 137 of 648
`
`

`

`— 136 —
`
`60950—1©|EC:2005+A1:2009
`+A2:2013
`
`Compliance is checked by inspection.
`
`3.3.8 Stranded wire
`
`The end of a stranded conductor shall not be consolidated by soft soldering at places where
`the conductor is subject to contact pressure unless the method of clamping is designed so as
`to reduce the [ikelihood of a bad contact due to cold flow of the solder.
`
`Spring terminals that compensate for the cold flow are deemed to satisfy this requirement.
`
`Preventing the clamping screws from rotating is not considered to be adequate.
`
`insulated so that. should a strand of a flexible
`Terminals shall be located. guarded or
`conductor escape when the conductor is fitted, there is no likelihood of accidental contact
`between such a strand and
`
`—
`
`7
`
`accessible conductive parts, or
`
`parts
`conductive
`unearthed
`SUPPLEMENTARY INSULATION only.
`
`separated
`
`from accessible
`
`conductive
`
`parts
`
`by
`
`Compliance is checked by inspection and, unless a special cord is prepared in such a way as
`to prevent the escape of strands, by the following test.
`
`A piece of insulation approximately 8 mm long is removed from the end of a flexible conductor
`having the appropriate nominal cross-sectional area. One wire of the stranded conductor is
`left free and the other wires are fully inserted into, and clamped in the terminai.
`
`the free wire is bent in every possible direction, but
`Without tearing the insulation

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket