throbber
— 182 —
`
`60950-1 © IEC:2005+A1:2009
`+A2:2013
`
`—
`
`—
`
`Table 55 using the PEAK WORKING VOLTAGE (U), as determined in 2.10.2; or
`
`Table 50 using the REQUIRED WITHSTAND VOLTAGE, as determined in G.4.
`
`In various places in this standard, special electric strength tests or test voltages are specified for certain
`NOTE 1
`situations. The test voltages in 52.2 do not apply to these situations.
`NOTE 2 For consideration of temporary cvervoltages, see JEC 806644.
`
`it is permitted to use
`For equipment in Overvoltage Categoryl and Overvoltage Category it,
`either Table 5B or Table 50. However, for a SECONDARY CIRCUIT that is neither connected to
`protective earth nor provided with a protective screen in accordance with 2.6.1 9), Table 5C
`shall be used.
`
`For equipment in Overvoltage Category Ill and Overvoltage Category lV, Table SC shall be
`used.
`
`The voltage applied to the insulation under test is gradually raised from zero to the prescribed
`voltage and held at that value for 60 s.
`
`Where, elsewhere in this standard, ROUTINE TESTS are required to be conducted in accordance
`with 5.2.2,
`it is permitted to reduce the duration of the electric strength test to 1 s and to
`reduce the test voltage permitted in Table 50, if used, by 10 %.
`
`There shall be no insulation breakdown during the test.
`
`insulation breakdown is considered to have occurred when the current that flows as a result of
`the application of the test voltage rapidly increases in an uncontrolled manner,
`that is the
`insulation does not restrict the flow of the current. Corona discharge or a single momentary
`fiashover is not regarded as insulation breakdown.
`
`in contact with the insulating surface. This
`insulation coatings are tested with metal foil
`procedure is limited to places where the insulation is likely to be weak, for example, where
`there are sharp metal edges under the insulation.
`lf practicable, insulating linings are tested
`separately, Care is taken that the metal foil is so placed that no tlashover occurs at the edges
`of the insulation. Where adhesive metal foil is used, the adhesive shall be conductive.
`
`To avoid damage to components or insulation that are not involved in the test, disconnection
`of integrated circuits or the like and the use of equipotential bonding are permitted.
`
`For equipment incorporating both REINFORCED lNSULATlON and lower grades ofinsulation, care
`is taken that the voltage applied to the REINFORCED INSULATION does not overstress BASIC
`INSULATION or SUPPLEMENTARY INSULATION.
`
`NOTES Where there are capacitors across the insulation under
`capacitors), it is recommended that do. test voltages are used.
`NOTE 4 Components providing a (1.0. path in parallel with the insulation to be tested, such as discharge resistors
`for filter capacitors, voltage limiting devices or surge suppressors, should be disconnected.
`
`radio—frequency filter
`
`test
`
`(for example,
`
`transformer winding varies along the length of the winding in
`Where insulation of a
`accordance with 2.10.1.5, an electric strength test method is used that stresses the insulation
`accordingly.
`
`NOTE 5 An example of such a test method is an induced voltage test that is applied at a frequency sufficiently
`high to avoid saturation of the transformer. The input voltage is raised to a value that would induce an output
`voltage equal to the specified test voltage.
`
`No test is applied to FUNCTIONAL INSULATION, unless 5.3.4 b) has been selected.
`
`Page 184 of 648
`
`VOLTSERVER EXHIBIT 1023 (part 4 of 11)
`
`

`

`60950—1 © IEC:2005+A1:2009
`+A2i2013
`
`— 183 —
`
`Table SB — Test voltages for electric strength tests
`based on peak working voltages
`Part 1
`
`WORKING VOLTAGE U
`
` Points of application (as appropriate)
`PRIMARY CIRCUIT t0 BODY
`SECONDARY CIRCUIT t0 BODY
`
`
`PRIMARY CIRCUIT to SECONDARY CIRCUIT
`between independent
`
`
`SECONDARY CIRCUITS
`
`
`between parts in PRIMARY CIRCUITS
`
`
`
`
`WORKING VOLTAGE U, peak or d.c.
`
`
`
`Grade of
`Over 42,4 V
`
`Insulation
`peak or
`
`
`Over
`Over
`Over 10 kV
`Up to and
`
`
`
`Up to and
`210 v up
`0"” 420 V
`Up to and
`including
`60 V d'c‘
`1,41 kV up
`
`
`
`
`including
`to and
`IlnpcltgdiIgd
`including
`42,4 V
`:Inpcltgdaigd
`to and
`
`
`
`
`
` 420Vb ‘10ch
`210 V a
`including
`50 kV
`peak or
`10 M! g
`141 ng
`including
`
`
`
` Test voltage. volts a.c. r.m.s.
`
` FUNCTIONAL 1 000 1 500 see Va see V3
`
`
`
`in Table 5B,
`in Table SB,
`‘In Table 58,
`part 2
`part 2
`part 2
`see Ifa
`see Va
`see Va
`BASIC, SUPPLE—
`
`
`
`
`in Table SE,
`MENTARY
`in Table SB,
`in Table SB,
`
`
`
`
`part 2
`part 2
`part 2
`
`
`see l/b
`REINFORCED
`see Vb
`
`In Table SB.
`in Table 58.
`
`part 2
`
`part2
`
`For PEAK WORKING VOLTAGES exceeding 10 kV peak or do.
`in SECONDARY CIRCUITS, the same test voltages as
`
`for PRIMARY CIRCUITS apply.
`
`6 Use this column for unearthed DC MAINS SUPPLIES up to and including 210 V [see 2.10.3.2 (3)],
`b Use this column for unearthed Dc MAINS SUPPLIES over 210 V, up to and including 420 V [see 2103.2 (3)].
`c Use this column for unearthed DC MAINS SUPPLIES over 420 V [see 2.10.3.2 0)].
`
`‘1 Use these columns for do. derived within the equiment from an AC MAINS SUPPLY or for DC MAINS SUPPLIES
`
`that are earthed within the same building.
`
`
`
`
`
`
`Page 185 of 648
`
`

`

`— 184 —
`
`60950-1 © IEC:2005+A1:2009
`+A2:2013
`
`Table SB — Test voltages for electric strength tests
`based on peak working voltages
`Part2
`
`peak
`or d.c.
`
`34
`35
`35
`33
`40
`42
`44
`46
`43
`50
`52
`54
`55
`55
`50
`62
`64
`66
`55
`70
`?2
`74
`75
`15
`50
`85
`90
`95
`100
`105
`110
`115
`120
`125
`130
`135
`140
`145
`150
`152
`a155
`a160
`a155
`3170
`e175
`e130
`“184
`135
`190
`200
`210
`220
`230
`240
`
`Linear interpolation is permitted between the nearest two points.
`
`a At these voltages, the values of Vb are determined by the general curve Vb: 155,86 U546“ and are not 1,6 Va.
`
`
`
`l1111111111111111111111
`
`11111111111111111’
`
`Page 186 of 648
`
`

`

`60950-1 © |EC:2005+A1:2009
`+A2:2013
`
`—— 185 —
`
`Table 5C — Test voltages for electric strength tests
`based on required withstand voltages
`
`
` Test voltage for Fm,
`Test voltage for
`REINFORCED INSULATION
`BASIC INSULATION or
`REQUIRED WITHSTAND VOLTAGE
`
`SUPPLEMENTARY INSULATION
`
`
`
`up to and including
`
`kV peak at: or d.c.
`kV peak
`
`
`
`@735 0,33
`
`
`07550.5
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`Linear interpolation is permitted between the nearest two points.
`If FUNCTIONAL INSULATION is tested (as required by 53.4 b), the test voltage for 3 WORKING VOLTAGE up to and
`
`including 42,4 V peak or 60 V dc. shall not exceed 707 V peak or do. For a higher WORKING VOLTAGE, the test
`
`voltage given in Table SB or Table 50 is used.
`
`a U is any REQUIRED WITHSTAND VOLTAGE higher than 12,0 kv.
`
`
`5.3
`
`Abnormal operating and fault conditions
`
`5.3.1
`
`Protection against overload and abnormal operation
`
`Equipment shall be so designed that the risk of fire or electric shock due to mechanical or
`electrical overload or failure, or due to abnormal operation or careless use, is limited as far as
`practicable.
`
`After abnormal operation or a single fault (see 1.4.14), the equipment shall remain safe for an
`OPERATOR in the meaning of this standard, but it is not required that the equipment should still
`be in full working order.
`It
`is permitted to use fusible links, THERMAL CUT-OUTS, overcurrent
`protection devices and the like to provide adequate protection.
`
`Compliance is checked by inspection and by the tests of 5.3. Before the start of each test, it is
`checked that the equipment is operating normally.
`
`if a component or subassembly is so enclosed that short—circuiting or disconnection as
`specified in 5.3 is not practicable or is difficult to perform without damaging the equipment,
`it
`is permitted to make the tests on sample parts provided with special connecting leads. if this
`is not possible or not practical,
`the component or subassembly as a Whole shall pass the
`tests.
`
`Equipment is tested by applying any condition that may be expected in normal use and
`foreseeable misuse.
`
`is tested with the covering
`in addition, equipment that is provided with a protective covering,
`in place under normal idling conditions until steady conditions are established.
`
`Page 187 of 648
`
`

`

`H 186 e
`
`60950—1 © IEC:2005+A1:2009
`+A222013
`
`5.3.2 Motors
`
`Under overload, locked rotor and other abnormal conditions, motors shall not create a hazard
`due to excessive temperatures.
`
`—
`
`NOTE Methods of achieving this include the following:
`—
`the use of motors that do not overheat under locked-rotor conditions (protection by inherent or external
`impedance);
`the use in SECONDARY CIRCUITS of motors that may exceed the permitted temperature limits but that do not
`create a hazard;
`a the use of a device responsive to motor current;
`- the use of an integral THERMAL CUT-OUT;
`— the use of a sensing circuit that disconnects power from the motor in a sufficiently short time to prevent
`overheating if, for example, the motor fails to perform its intended function.
`
`Compliance is checked by the applicable test of Annex 8.
`
`5.3.3 Transformers
`
`Transformers shall be protected against overload, for example, by
`
`—
`
`e
`
`e
`
`overcurrent protection,
`
`internal THERMAL CUT~OUTS, or
`
`use of current limiting transformers.
`
`Compliance is checked by the applicable tests of Clause C. 1.
`
`5.3.4 Functional insulation
`
`For FUNCTIONAL INSULATION, CLEARANCES and CREEPAGE DISTANCES shall satisfy one Of the
`following requirements a) or b) or c).
`
`is
`For insulation between a SECONDARY CIRCUIT and an inaccessible conductive part that
`earthed for functional reasons, CLEARANCEs and CREEPAGE DISTANCES shall satisfy a) or b)
`or c).
`
`the CLEARANCE and CREEPAGE DISTANCE requirements
`a) They meet
`INSULATION in 2.10 (or Annex G).
`
`for
`
`FUNCTIONAL
`
`b) They withstand the electric strength tests for FUNCTIONAL INSULATION in 5.2.2.
`0) They are short-circuited where a short-circuit could cause
`
`-
`
`-
`
`overheating of any material creating a risk of fire, unless the material that could be
`overheated is of V4 CLASS MATERIAL, or
`
`thermal damage to BASIC INSULATION, SUPPLEMENTARY INSULATION or REINFORCED
`INSULATION, thereby creating a risk of electric shock.
`
`Compliance criteria for 5.3.4 o) are in 5.3.9.
`
`5.3.5 Electromechanicalcomponents
`
`Where a hazard is likely to occur, electromechanical components other than motors are
`checked for compliance with 5.3.1 by applying the following conditions:
`
`— mechanical movement shall be locked in the most disadvantageous position while the
`component is energized normally; and
`
`_
`
`in the case of a component that is normally energized intermittently, a fault shall be
`simulated in the drive circuit to cause continuous energizing of the component.
`
`Page 188 of 648
`
`

`

`60950—1 © lEC:2005+A1:2009
`+A222013
`
`_ 187 H
`
`The duration of each test shall be as follows:
`
`— for equipment or components whose failure to operate is not evident to the OPERATOR: as
`long as necessary to establish steady conditions or up to the interruption of the circuit due
`to other consequences of the simulated fault condition, whichever is the shorter; and
`
`—
`
`for other equipment and components: 5 min or up to interruption of the circuit due to a
`failure of the component
`(for example, burn-out) or to other consequences of the
`simulated fault condition, whichever is the shorter.
`
`For compliance criteria see 5.3.9.
`
`5.3.6 Audio amplifiers in information technology equipment
`
`Equipment having audio amplifiers shall be tested in accordance with 4.3.4 and 4.3.5 of
`lEC 60065. The equipment shall be operating normally before the tests are conducted.
`
`5.3.7 Simulation of faults
`
`For components and circuits other than those covered by 5.3.2, 5.3.3, 5.3.5 and 5.3.6,
`compliance is checked by simulating single fault conditions (see 1.4.14).
`
`In Canada and the United States, additional requirements for overloading and other fault simulation for
`NOTE 1
`internal circuit connections apply.
`
`The following faults are simulated.
`
`a) Short—circuit or disconnection of any components in PRIMARY CIRCUITS.
`
`b) Short-circuit or disconnection of any components where failure could adversely affect
`SUPPLEMENTARY lNSULATlON or REINFORCED lNSULA TION.
`
`c) Short-circuit, disconnection or overloading of all relevant components and parts unless
`they comply with the requirements of 4. 7.3.
`NOTE 2 An overload condition is any condition between NORMAL LOAD and maximum current condition up to
`short-circuit.
`
`d) Faults arising from connection of the most unfavourable load impedance to terminals and
`connectors that deliver power from the equipment, other than mains power outlets.
`
`e) Other single faults specified in 1.4.14.
`
`Where there are multiple outlets having the same internal circuitry,
`one sample outlet.
`
`the test is only made on
`
`For components in PRlMARY ClRCUlTS associated with the mains input, such as the supply
`cord, appliance couplers. EMC filtering components, switches and their interconnecting
`wiring, no fault is simulated, provided that the component complies with 5.3.4 a) or 5.3.4 b).
`
`NOTE 3 Such components are still subject to other requirements of this standard where applicable,
`1.5.1, 2.105.413 and 5.2.2.
`
`including
`
`in addition to the compliance criteria given in 5.3.9, temperatures in the transformer supplying
`the component under test shall not exceed those specified in Clause 0.1, and account shall
`be taken of the exception detailed in Clause 6.1 regarding transformers that would require
`replacement.
`
`5.3.8 Unattended equipment
`
`Equipment intended for unattended use and having THERMOSTATS, TEMPERATURE LIMITERs and
`THERMAL CUT-OUTS, or having a capacitor not protected by a fuse or the like connected in
`parallel with the contacts, is subjected to the following tests.
`
`Page 189 of 648
`
`

`

`— 188 —
`
`60950-1 © |EC:2005+A1:2009
`+A2:2013
`
`Equipment is operated under the conditions specified in 4.5.2 and any control that serves to
`limit
`the temperature is short-circuited.
`if the equipment is provided with more than one
`THERMOSTAT, TEMPERATURE LlMlTER or THERMAL CUT—OUT, each is short-circuited, one at a time.
`
`lf interruption of the current does not occur, the equipment is switched off as soon as steady
`conditions are established and is permitted to cool down to approximately room temperature.
`
`'
`
`the
`repeated until
`is
`the test
`intended for continuous operation,
`For equipment not
`temperature has stabilized, regardless of any marking of RATED OPERATlNG TlME or RATED
`RESTlNG TiME. For this test the THERMOSTATS, TEMPERATURE LiMiTERs and THERMAL cur-ours
`are not short-circuited.
`
`lf in any test a MANUAL RESET THERMAL CUT-OUT operates, or if the current is otherwise
`interrupted before the temperature has stabilized,
`the heating period is taken to have ended,"
`but if the interruption is due to the rupture of an intentionally weak part, the test is repeated
`on a second sample. Both samples shall comply with the conditions specified in 5.3.9.
`
`5.3.9 Compliance criteria for abnormal operating and fault conditions
`
`5.3.9.1 During the tests
`
`During the tests of 5.3.4 0), 5.3.5, 5.3.7, 5.3.8 and Clause C. 1:
`
`— ifa fire occurs, it shall not propagate beyond the equipment; and
`
`— the equipment shall not emit molten metal; and
`
`— ENCLOSURES shall not deform in such a way as to cause non—compliance with 2.1.1, 2.6.1,
`2.10.3 (orAnnex G) and 4.4.1.
`
`the temperatures of
`Moreover, during the tests of 5.3.7 0), unless otherwise specified,
`insulating materials other than thermoplastic materials shall not exceed those in Table 5D.
`
`Table 5D — Temperature limits for overload conditions
`
`Maxim um tem peratu re “0
`
`Thermal class
`
`parentheses.
`
`The designations A to H, formerly assigned in IEC 60085 to thermal classes 105 to 180, are given in
`
`if the failure of the insulation would not result in HAZARDOUS VOLTAGE-'8 or HAZARDOUS ENERGY
`LEVELS becoming accessible,
`a maximum temperature of 300 “C is permitted. Higher
`temperatures are permitted for insulation made of glass or ceramic material.
`
`5.3.9.2
`
`After the tests
`
`After the tests of 5.3.4 c), 5.35, 5.3.7 and 5.3.8 and Clause C. 1, an electric strength test
`according to 5.2.2 is made on:
`
`—
`
`—
`
`7
`
`REINFORCED lNSULATiON,' and
`
`BASIC iNSULATlON Oi‘ SUPPLEMENTARY lNSULATlON forming part Of DOUBLE iNSULATiON,‘ and
`
`BASIC iNSULATlON between the PRIMARY ClRCUlT and the main protective earthing terminal;
`
`Page 190 of 648
`
`

`

`609504 © |EC:2005+A1:2009
`+A212013
`
`— 189 —
`
`if any of the following applies:
`
`e
`
`—
`
`—
`
`the CLEARANCE or CREEPAGE DISTANCE has been reduced below the value specified in 2.10
`(orAnnex G); or
`
`the insulation shows visible signs of damage; or
`
`the insulation cannot be inspected.
`
`6 Connection to telecommunication networks
`
`It the equipment is to be connected to a TELECOMMUNECATION NETWORK, the requirements of
`Clause 6 apply in addition to the requirements of Clauses 1 to 5 in this standard.
`
`is assumed that adequate measures according to ITU-T Recommendation Kit have been taken to
`It
`NOTE 1
`reduce the likelihood that the overvoltages presented to the equipment exceed 1,5 kV peak,
`In installations where
`overvoltages presented to the equipment may exceed 1.5 kV peak, additional measures such as surge suppression
`may be necessary.
`NOTE2 Legal
`requirements may exist regarding the connection of
`TELECOMMUNICATLON NETWORK operated by a public network operator.
`NOTE 3
`"he requirements of 2.3.2. 6.1.2 and 6.2 can apply to the same physical insulation or CLEARANCE.
`
`a
`NOTE 4
`"he Ac MAINS SUPPLY system,
`it used as
`a
`communication transmission medium,
`is not
`TELECOMMUNICATION NETWORK (see 1.2.13.8), and Clause 6 does not apply. The other clauses of this standard will
`apply to coupling components, such as signal transformers, connected between the mains and other circuitry. The
`requirements for DOUBLE lNSULATION or RElNFORCED INSULATION will generally apply. See also IEC 60664-1 and
`Annex Z of this standard for overvoEtages to be expected at various points in the Ac MAINS SUPPLY system.
`NOTE 5
`In Canada and the United States, additional requirements apply for TNV CIRcuns for protection from
`overvoltage due to power line cross (telecommunication line contact with a power line),
`induction and earth
`potential rise from power line fault current.
`
`information technology equipment
`
`to a
`
`6.1
`
`Protection of telecommunication network service persons, and users
`of other equipment connected to the network, from hazards in the equipment
`
`6.1.1
`
`Protection from hazardous voltages
`
`Circuitry intended to be directly connected to a TELECOMMUNICATION NETWORK shall comply
`with the requirements for an SELV CIRCUIT or a TNV CIRCUIT.
`
`Where protection of the TELECOMMUNiCATION NETWORK relies on the protective earthing of the
`equipment, the installation instructions and other relevant literature shall state that integrity of
`protective earthing shall be ensured, see also 1.7.2.1.
`
`Compliance is checked by inspection and measurement.
`
`6.1.2 Separation of the telecommunication network from earth
`
`6.1.2.1 Requirements
`
`there shall be insulation between circuitry intended to be
`Except as specified in 6.1.2.2,
`connected to a TELECOMMUNICATION NETWORK and any parts or circuitry that will be earthed in
`some applications, either within the EUT or via other equipment.
`
`Surge suppressors that bridge the insulation shall have a minimum rated operating voltage
`UOp (for example, the sparkover voltage of a gas discharge tube) of
`
`Uop : Upeak + AUsp + AUse
`
`where
`
`Upeak
`
`is one of the following values:
`for equipment intended to be installed in an area where the
`nominal voltage of the AC MAINS SUPPLY exceeds 130 V:
`
`360 V
`
`Page 191 of 648
`
`

`

`— 190 —
`
`60950-1 © lEC:2005+A1:2009
`+A2:2013
`
`AUSp
`
`AUSa
`
`in
`the rated operating voltage due to variations
`the maximum increase of
`is
`component production.
`If this is not specified by the component manufacturer, cusp
`shall be taken as 10 % ot the rated operating voltage of the component.
`
`is the maximum increase of the rated operating voltage due to the component ageing
`over the expected life of the equipment.
`If this is not specified by the component
`manufacturer, AUSa shall be taken as 10 % of the rated operating voltage of the
`component.
`
`NOTE 1
`
`(AU5p + AU“) may be a single value provided by the component manufacturer.
`
`Compliance is checked by inspection and by the following tests. The dimensional and
`construction requirements of 2.10 and Annex (3 do not apply for compliance with 6.1.2.
`
`In Finland, Norway and Sweden. there are additional requirements for the insulation. For the complete
`NOTE 2
`text, see EN 60950-1:2—OQ-X—2006.
`
`insulation is subjected to an electric strength test according to 5.2.2. The ac. test voltage is
`as follows:
`
`— for equipment intended to be installed in an area where the
`nominal AC MAlNS SUPPLY voltage exceeds 130 V:
`
`e for all other equipment:
`
`1,5 kV
`
`1,0 kV.
`
`The test voltages apply whether or not the equipment is powered from the AC MAINS SUPPLY.
`
`Components bridging the insulation that are left in place during electric strength testing shall
`not be damaged. There shall be no breakdown of insulation during electric strength testing.
`
`it is permitted to remove components that bridge the insulation, other than capacitors, during
`electric strength testing.
`
`if this option is chosen, an additional test with a test circuit according to Figure 6A is
`performed with all components in place.
`
`For equipmentpowered from an AC MAlNS SUPPLY, the test is performed with a voltage equal to
`the RATED VOLTAGE of the equipment or to the upper voltage of the RATED VOLTAGE RANGE. For
`equipment powered from a no MAlNS SUPPLY, the test is performed with a voltage equal to the
`highest nominal voltage of the AC MAlNS SUPPLY in the region where the equipment is to be
`used, for example, 230 V for Europe or 120 V for North America.
`
`The current flowing in the test circuit of Figure 6A shall not exceed 10 mA.
`
`Page 192 of 648
`
`

`

`60950-1 © |EC:2005+A1:2009
`+A212013
`
`— 191 —
`
`Components bridging
`the insulation, for example,
`
`surge suppressors
`Connection for
`MAINS SUPPLY
`]
`0
`Connection for
`
`(not connected)
`em. .-
`3 TELECOMUNlCATION
`NETWORK
`(not connected)
`
`Insulation
`
`'
`
`
`
`
`o
`
`I
`
`
`
`EDT
`
`Connection for
`
`protective earth
`or parts or circuitry
`to be connected to
`protective earth
`
`Rated voltage
`
`‘ ._-_____._.. mA . “-7...
`
`.__.i0
`
`5 000 Q
`
`
`rec
`
`1567/05
`
`Figure 6A — Test for separation between a telecommunication network and earth
`
`6.1.2.2 Exclusions
`
`The requirements of6.1.2.1 do not apply to any of the following:
`
`fl
`
`m
`
`,
`
`PERMANENTLY CONNECTED EQUIPMENT Oi" PLUGGABLE EQUIPMENT TYPE B;
`
`intended to be installed by a SERVICE PERSON and has installation
`is
`that
`equipment
`instructions that require the equipment to be connected to a socket-outlet with a protective
`earthing connection (see 6.1.1);
`
`a permanently connected PROTECTIVE EARTHING
`that has provision for
`equipment
`CONDUCTOR and is provided with instructions for the installation of that conductor.
`
`the exclusions are applicable only for PERMANENTLY CONNECTED
`NOTE In Finland, Norway and Sweden,
`EQUIPMENT, PLUGGABLE EQUIPMENT TYPE B and equipment intended to be used in 3 RESTRICTED ACCESS LOCATION
`where equipotential bonding has been appiied,
`for example,
`in a telecommunication centre, and which has
`provision for a permanentiy connected PROTECTIVE EARTHING CONDUCTOR and is provided with instructions for the
`installation of that conductor by a SERVICE PERSON.
`
`6.2
`
`Protection of equipment users from overvoltages on telecommunication
`networks
`
`6.2.1 Separation requirements
`
`separation between a
`Equipment shall provide adequate electrical
`TNV-a CIRCUIT and the following parts of the equipment.
`
`TNV«1 CIRCUIT or a
`
`a) Unearthed conductive parts and non- conductive parts of the equipment expected to be
`held or teaches otherwise maintained in continuous contact with the body during normal
`use (for example a telephone handset a—keybeard—er—the—eehw—exteaer- or headset or the
`palm rest surface of a laptop or notebook computer).
`
`b) Parts and circuitry that can be touched by the test finger, Figure 2A (see 2.1.1.1), except
`contacts of connectors that cannot be touched by the test probe, Figure 20 (see 21.1.1).
`
`0) An SELV CIRCUIT, a TNV—2 CIRCUIT or a LIMITED CURRENT CIRCUIT provided for connection of
`other equipment. The requirement for separation applies whether or not
`this circuit
`is
`accessible.
`
`These requirements do not apply where circuit analysis and equipment investigation indicate
`that adequate protection is assured by other means, for example, between two circuits each
`of which has a permanent connection to protective earth.
`
`Page 193 of 648
`
`

`

`— 192 —
`
`60950-1 © |EC:2005+A1:2009
`+A2:2013
`
`Compliance is checked by inspection and by the tests of 6.2.2. The dimensional and
`constructional requirements of 2. 10 and Annex G do not apply for compliance with 6.2.1.
`
`NOTE The requirements of 2.10 and Annex G may apply for compliance with 2.2 and 2.3. See Footnote e and
`Footnote f of Table 2H.
`
`Connection for
`AC MAINS SUPPLY
`(not connected)
`
`“J
`
`L
`N
`
`PE
`
`
`
`
`
`
`Connection for
`TELECDMUNICATION
`NETWORK
`(not connected)
`
`EUT
`
`/
`Linked for
`
`c) only
`
`handheld parts
`
` *Typical for
`
`
`
`Conductive foil
`
`Test voltage
`
`
`generator
`
`lEC 156265
`
`Figure BB — Application points of test voltage
`
`6.2.2 Electric strength test procedure
`
`Compliance with 6.2.1 is checked by the test of either 6.2.2.1 or 6.2.2.2.
`
`NOTE In Australia, the—teste—ot—both-S—E—QA—and—é-Q—Q—Z—appty- a value of 3 0 W is used for 6.21 a) equipment
`and 1 5 kV for 6 2 1 b) and 6 2 1 c) equipment. These values have been determined considering the low frequency
`induced voltages from the power suppiy distribution system
`
`if a test is applied to a component (see 1.4.3), for example, a signal transformer, which is
`clearly intended to provide the separation required,
`the component shall not be bypassed by
`other components, mounting devices or wiring, unless these components or wiring also meet
`the separation requirements of 6.2.
`
`For the tests, all conductors intended to be connected to the TELECOMMUNICATION NETWORK
`are connected together
`(see Figure 68),
`including any conductors
`required by the
`TELECOMMUNICATlON NETWORK authority to be connected to earth. Similarly, all conductors
`intended to be connected to other equipment are connected together for testing related to
`6.2.1 c).
`
`Non-conductive parts are tested with metal foil in contact with the surface. Where adhesive
`metal foil is used, the adhesive shall be conductive.
`
`Page 194 of 648
`
`

`

`60950-1©IEC:2005+A1:2009
`+A2:2013
`
`— 193 —
`
`6.2.2.1
`
`Impulse test
`
`The electrical separation is subjected to ten impulses of alternating polarity, using the impulse
`test generator reference 1 of Table N. 1, The interval between successive impulses is 60 s and
`U0 is equal to:
`
`— for 6.2.1 a):
`
`2,5 kV; and
`
`— for 6.2.1 b) and 6.2.1 c):
`
`1,5 kV.
`
`NOTE 1 The value of 2,5 M! for 62.1 a) has been chosen primarily to ensure the adequacy of the insulation
`concerned and it does not necessarily simulate likely overvoltages.
`
`NOTE 2
`
`In Australia, a value of UC = 7,0 W is used in 6.2.1 a) for hand-held telephones and for headsets.
`
`6.2.2.2 Steady—state test
`
`The electrical separation is subjected to an electric strength test according to 5.2.2.
`
`The as. test voltage is:
`
`— for 6.2.1 3):
`
`1,5 kl/,' and
`
`— for 6.2.1 b) and 6.2.10):
`
`1,0 RV.
`
`NOTE In Australia, a value of 3,0 M! is used in 6.21 a) for handheld telephones and headsets and 2,5 M! for
`other equipment,
`to simulate lightning surges on typical rural and semi rural network lines. A value of 1,5 l-(V is
`used in 62.1 b) and c).
`
`it is permitted to remove surge suppressors, provided that such
`For 6.2.1 b) and 6.2.1 0),
`devices pass the impulse test of 6.2.2.1 for 6.21 b) and 6.2.1 0) when tested as components
`outside the equipment. For 6.21 a), surge suppressors shall not be removed.
`
`6.2.2.3 Compliance criteria
`
`During the tests of 62.21 and 6.2.22, there shall he no breakdown of insulation.
`
`insulation breakdown is considered to have occurred when the current that flows as a result of
`the application of the test voltage rapidly increases in an uncontrolled manner,
`that is the
`insulation does not restrict the flow of current.
`
`if a surge suppressor operates (or sparkover occurs within a gas discharge tube) during the
`test:
`
`—
`
`—
`
`2
`
`for 6.2.1 a), such operation represents a failure; and
`
`for 6.2.1 b) and 6.2.1 C), such operation is permitted during the impulse test; and
`
`for 6.2.1 b) and 6.2.1c), such operation during the electric strength test (by any surge
`suppressor left in place) represents a failure.
`
`For impulse tests, damage to insulation is verified in one of two ways, as follows:
`
`—
`
`fl
`
`during the application of the impulses, by observation of oscillograms. Surge suppressor
`operation or breakdown through insulation is judged from the shape of an oscillogram.
`
`after application of all the impulses, by an insulation resistance test. Disconnection of
`surge suppressors is permitted while insulation resistance is being measured. The test
`voltage is 500 Vd.c. or,
`if surge suppressors are left in place, a dc. test voltage that is
`10% less than the surge suppressor operating or striking voltage. The insulation
`resistance shall not be less than 2 M9.
`
`NOTE A description of procedures to judge whether a surge suppressor operation or breakdown of insulation has
`occurred, using oscillograms, is given in Annex 8.
`
`Page 195 of 648
`
`

`

`— 194 —
`
`609504 © |EC:2005+A1:2009
`+A212013
`
`6.3
`
`Protection of the telecommunication wiring system from overheating
`
`Equipment intended to provide power over the telecommunication wiring system to remote
`equipment shall
`limit
`the output current
`to a value that does not cause damage to the
`telecommunication wiring system, due to overheating, under any external load condition. The
`maximum continuous current from equipment shall not exceed a current limit that is suitable
`for the minimum wire gauge specified in the equipment installation instructions. The current
`limit is 1,3 A if such wiring is not specified.
`
`NOTE 1 The overcurrent protective device may be a discrete device such as a fuse. or a circuit that performs that
`function.
`
`for which the
`NOTE 2 The minimum wire diameter normally used in telecommunication wiring is 0,4 mm,
`maximum continuous current for a multipair cable is 1,3 A. This wiring is not usually controlled by the equipment
`installation instructions, since the wiring is often installed independent of the equipment installation.
`NOTE 3 Further current limitation may be necessary for equipment intended for connection to networks that are
`subject to overvoltages, due to operating parameters for protective devices.
`
`Compliance is checked as follows.
`
`if current limiting is due to the inherent impedance of the power source, the output current into
`any resistive load,
`including a short-circuit,
`is measured. The current
`limit shall not be
`exceeded after 60 s of test.
`
`limiting is provided by an overcurrent protective device having a specified
`if current
`time/current characteristic:
`
`u
`
`the time/current characteristic shall show that a current equal to 110 % of the current limit
`will be interrupted within 60 min; and
`NOTE 4 Timelcurrent characteristics of type 90 and type gN fuses specified in IEC 80269-2—1 comply with the
`above limit. Type 9D or type gN fuses rated 1 A, would meet the 1,3 A current limit.
`
`—
`
`including a short-circuit, with the overcurrent
`the output current into any resistive load,
`protective device bypassed, measured after 603 of test, shall not exceed 1000/U,
`where U is the output voltage measured in accordance with 1.4.5 with all load circuits
`disconnected.
`
`if current limiting is provided by an overcurrent protective device that does not have a
`specified time/current characteristic:
`
`—
`
`—
`
`the output current into any resistive load,
`current limit after 60 s of test; and
`
`including a short—circuit, shall not exceed the
`
`including a short-circuit, with the overcurreni
`the output current into any resistive load,
`protective device bypassed, measured after 60 s of test, shall not exceed 1 GOO/U, where
`U is
`the output voltage measured in accordance with 1.4.5 with all
`load circuits
`disconnected.
`
`7 Connection to cable distribution systems
`
`7.1
`
`General
`
`the requirements of
`If the equipment is to be connected to a CABLE DISTRIBUTION SYSTEM,
`Clause 7 apply in addition to the requirements of Clauses 1 to 5 of this standard.
`
`NOTE 1 Unless the connection uses coaxial cable, the circuit is not a CABLE DISTRIBUTION SYSTEM, and Clause 6
`applies.
`is assumed that adequate measures have been taken to reduce the likelihood that
`it
`NOTE 2
`overvoltages presented to the equipment exceed the following values:
`e
`10 kV for equipment to be connected only to an outdoor antenna;
`e 4 kV to other equipment, see ITUwT Recommendations K.20, K.21 and K.45.
`in installations where overvoltages presented to the equipment may exceed t

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket